Sanyo XHW4272R dimensions Power, 230/208/1/60, Compressor, Outdoor Unit, Indoor Unit, Refrigerant

Models: XHW4272R

1 2
Download 2 pages 30.58 Kb
Page 1
Image 1
Split System Submittal Data

Split System Submittal Data

System: 42XW72R Indoor/Outdoor: XHW4272R/C4272R

Grille: PNR-XH3642

Ceiling Recessed Air Conditioner

Print Form

Job Name:

Location:

Engineer:

Submitted to:

Submitted by:

Reference:

 

General Data (at 230V)

Power

V/PH/Hz

230/208/1/60

Circuit Ampacity

(A)

15-40 Indoor-Outdoor

Fuse Size, Max.

(A)

15-40 Indoor-Outdoor

Compressor

 

DC Rotary Inverter

No. used

 

1

R.L. Amps - L.R.

(A)

18.1-31

Outdoor Unit

 

 

Fan type

 

Propeller

Dia. (in.) - No. Speeds

 

18-7/64-2

Type Drive - No. Speeds

 

DC Motor

No. Poles

(RPM)

8 - 830

No. Motors

(W)

1 - 90

CFM

(High)

3531

F.L. Amps

(A)

19.7

Coil Type

Aluminum Fin & Copper Pipe

Fin Type - Pipe Type

 

Slit Plate - Inner Rifed

Rows - F.P.I.

 

2 - 12.7

Face Area

(sq.ft.)

11.62

Tube Size

(in.)

3/8”

Indoor Unit

 

 

Fan type

 

Turbo

Dia. & Length (in.) - No. Speeds

17-7/16-1

No. Speeds

 

3 & Auto

No. Poles

(RPM, High)

6-506

No. Motors

(W)

1 - 60

CFM

(HI/Med/Lo)

1050/840/720

Indoor Sound Rating

(Hi) (dB-A)

45

F.L. Amps

(A)

1.0

Coil Type

Aluminum Plate Fin & Copper Tube

Fin Type - Pipe Type

 

Slit Plate - Inner Rifed

Rows - F.P.I.

 

2-14.9

Face Area

(sq.ft.)

8.2

Tube Size

(in.)

9/32”

Drain Connection Size

(in.)

1-17/64

Approval:

Date:

Construction:

Unit #:

Drawing #:

Refrigerant

 

 

 

 

 

R410A

Lbs. - R410a (outdoor unit)

 

 

 

7.94

Control

 

 

 

 

Electric Expansion Valve

Connection

 

 

 

 

 

Flare

Line Length, Max (ft.)

 

 

 

 

 

165

Lift Difference, Max (ft.)

50 (outdoor lower), 100 (outdoor higher)

Line Size

 

(in. O.D. Discharge)

3/8”

Line Size

 

(in. O.D. Suction)

5/8”

Dimensions

 

(in.)

 

H x W x D

Indoor Unit

 

(Uncrated)

14-31/64 x 45-9/32 x 33-55/64

Outdoor Unit

 

(Crated)

 

12-13/32 x 44-19/64 x 33-9/32

(Uncrated)

 

 

48-7/16 x 37 x 13-3/8

 

(Crated)

 

52-3/8 x 39-31/32 x 16-3/32

Weight

 

 

Indoor

 

Outdoor

Net

 

(lbs.)

 

60

 

220

Shipping

 

(lbs.)

 

71

 

240

Shipping Volume

 

 

 

Indoor

 

Outdoor

 

(cu.ft.)

10.6

 

19.5

Performance Data @ ARI Standard Conditions (230/208V)

Cooling

 

 

 

 

 

 

Total Capacity

 

 

 

(BTU/H)

39,500 (9,500-39,500)

Sensible Capacity

 

 

 

(BTU/H)

 

23,530

Latent Capacity

 

 

 

(BTU/H)

 

15,970

SEER

 

 

 

 

 

14.6

Dehumidification

 

 

 

(Pints/H)

 

12.6

Amps

 

 

 

(A)

 

23.0/25.4

Power Inputs

 

 

 

(W)

 

4,520/4,520

Outdoor Sound Rating

(dB-A)

 

53

Page 1
Image 1
Sanyo XHW4272R dimensions Power, 230/208/1/60, Compressor, Outdoor Unit, Indoor Unit, Refrigerant, Dimensions, Weight