Electrical Specifications | Dimensions | |
Electrical Connections |
|
|
1. Initiating device circuits: |
|
|
Voltage range |
| |
Supervisory current | 4mA max. capacitor EOL |
|
Alarm current | 9mA max. resistor EOL |
|
180mA max. per zone |
|
2.Initiating devices per zone:
Up to 30 detectors, any combination of those in No. 3 below. Up to five waterflow switches may be used. Any number of direct shorting devices may be used. Wiring may be Style D (Class A) or Style B (Class B).
3.The UL identifiers for compatibility are the same as the model names specified below. Compatible Siemens Fire Safety detectors are:
Detector | Installation Instructions |
P/N | |
P/N | |
P/N | |
P/N | |
P/N | |
| P/N |
| P/N |
P/N | |
P/N | |
P/N | |
P/N | |
P/N |
4.All circuits are power limited to NFPA 70 per NEC 760. Each detector or group of detectors must use a two wire circuit of at least 18 AWG thermoplastic fixture wire enclosed in conduit, or 18 AWG limited energy shielded cable without conduit, if permitted by local building codes.
5.Total circuit resistance must not exceed 70 ohms, 40 ohms if relay bases are used.