Siemens FP-11 manual Application Data, Dimensions

Models: FP-11

1 4
Download 4 pages 15.85 Kb
Page 3
Image 3
Application Data

system alarm functions programmed into the system are activated. Each FP-11 detector can operate one remote alarm indicator, one auxiliary relay, or one audible base.

Detector sensitivity, calibration, and identification are dynamically supervised by the control panel. Detector sensitivity and pre-alarm levels are a function of the application chosen at the control panel and are controlled by the panel. If an alternate, non-FirePrint mode is selected, then the sensitivity can be changed from the control panel.

The DPU or FPI-32 Program/Test accessory is used to program and verify the detector’s address. The technician selects the accessory’s program mode to enter the desired address. The DPU or FPI-32 auto- matically sets and verifies the address and tests the detector. It also allows the user to change the device ID from that of an FP-11 to an older detector ID such as an ILP-1, ILPT-1, ILP-2, ID-60P or ID-60PT to allow for easy replacement of older detectors without the need of reprogramming the control panel.

The FPI-32 operates on AC power or rechargeable batteries, providing flexibility and convenience in programming and testing equipment almost anywhere. When in the test mode, the DPU or FPI-32 will perform a series of diagnostic tests without altering the address or other stored data, allowing technicians to determine if the detector is operating properly.

The FP-11 fire detector may be installed on the same initiating circuit with IL or ID series detectors (Photo- electric, thermal, or ionization), MSI series manual stations, TRI series interfaces, ICP output control devices, or CZM series of addressable, conventional zone modules.

All FP-11 detectors can be cleaned in the field, when required, by simply removing the detector cover and unsnapping the photo chamber. There is also the option of cleaning the interior of the detector with a clean, soft cloth or brush, or replacing the labyrinth and bug screen included in the detector maintenance kit, model DMK-11.

The FP-11 uses the low profile surface mounting base, model DB-11. This base mounts on a 4-inch octagon, square, or a single gang electrical box. The base utilizes screw clamp contacts for electrical connections and self-wiping contacts for increased reliability. The base can be used with the optional LK-11 detector locking kit which contains 50 detector locks and an installation tool, to prevent unauthorized removal of the detector head. The DB-11 base has integral decora- tive plugs to cover the outer mounting screw holes.

The FP-11 is electrically compatible with existing MXL detector accessories including relays, remote lamps, duct housings, and audible bases. With duct housings, a base adapter and new detector housing cover are required (order AD-11UK upgrade kit). To use existing DB-3S base or audible base, the FP-11 requires a DB- ADPT base adapter.

All FP-11 detectors are approved for operation within the UL specified temperature range of 32 to 100 degrees F (0 to 38 degrees C).

Application Data

Installation of the FP-11 series of fire detectors requires a two-wire circuit of 18 AWG (minimum) thermoplastic fixture wire enclosed in conduit, or 18 AWG limited energy, shielded cable without conduit, if permitted by local codes. Field wiring should conform to local and National Electric Codes and the control panel wiring specifications.

“T-tapping” is permitted only for Style 4 (Class B) wiring.

FP-11 fire detectors can be applied within the maxi- mum 30 foot center spacing (900 sq. ft. areas) as referenced in NFPA 72. This applications guideline is based on ideal conditions, specifically, smooth ceiling surfaces, minimal air movement, and no physical obstructions between potential fire sources and the detector. Do not mount detectors in close proximity to ventilation or heating and air conditioning outlets. Exposed joints or beamed ceilings may also affect safe spacing limitations for detectors. Should questions arise regarding detector placement, observe NFPA 72 guidelines.

Good fire protection system engineering and common sense dictate how and when fire detectors are installed and used. Contact your local Siemens Building Technologies, Fire Safety Division authorized sales outlet whenever you need assistance applying FirePrint in unusual applications. Be sure to follow NFPA guidelines, UL/ULC approved installation instructions, which are included with every detector, and local codes as for all fire protection equipment.

Dimensions

Page 3
Image 3
Siemens FP-11 manual Application Data, Dimensions