Sierra Monitor Corporation Model 2050/2060, ORDERING INFORMATION 2050-00Ammonia Gas Monitor

Models: 2050 2060

1 2
Download 2 pages 55.73 Kb
Page 2
Image 2
Model 2050/2060

Model 2050/2060

Ammonia and Halocarbon Gas Monitors

SPECIFICATIONS

Indicators:

Green LED for Monitor “ON”/Safe

 

Red LED for Alarm

Sensor Type:

Solid-state metal oxide semiconductor

Alarm Setpoint::

 

 

2050 Series

100 ppm NH3

2060 Series

R11

500 ppm

 

R12

500 ppm

 

R22

50 ppm

 

R113

100 ppm

 

R123

70 ppm

 

R134a

50 ppm

 

R141b

40 ppm

 

R142b

40 ppm

 

R500

40 ppm

 

R502

70 ppm

User adjustable with calibration over range of 50 to 500 ppm

Calibration Gas:

80 ppm Hydrogen (H2)

2050 Series

2060 Series

150 ppm Carbon Monoxide (CO)

Power:

9-24 VDC, 250 mA

Signal Output::

 

2050-00/2060-00

Nominal 5 volt DC, source 25 mA. SAFE

 

and ALARM Signals

 

0.5 AMP dry contact, 100 VDC, 130 VAC

 

and audible

Response Time:

Less than 90 seconds

Operating Temperature Range:

 

-4oto 158oF (-20oto 70oC)

Enclosure Material:

Polystyrene

Size:

5.6 x 3.1 x 2.1 in. (14.2 x 7.9 x 5.3 cm)

Weight:

0.3 lb (0.15 Kg)

ORDERING INFORMATION

2050-00 Ammonia Gas Monitor

2060-00 Refrigerant/Halocarbon Gas Monitor

1200-26 Gas Sensor Calibrator w/2 gas cylinders of calibration gas

1290-10Gas Cylinder - Carbon Monoxide, 150 ppm 1290-11Gas Cylinder - Hydrogen, 80 ppm

OTHER PRODUCTS

2102-00 Dual Channel Alarm Panel

Outline and Dimensions

of Model 2050/2060

Sierra Monitor Corporation 1991 Tarob Court Milpitas, CA 95035 (408) 262-6611 (800) 727-4377 FAX: (408) 262-9042

Visit our website: www.sierramonitor.com E-mail: sierra@sierramonitor.com

© 2005 Sierra Monitor Corp. Rev. A-9/15/05
Page 2