Skuttle Indoor Air Quality Products SEH-7100-000 Connecting to the Humidifier

Models: SEH-7100-000

1 6
Download 6 pages 24.74 Kb
Page 3
Image 3
STEP 9: Connecting to the Humidifier

NOTE:

The humidifier control will operate properly with either a switched or continuous power source. Whether you are using accessory terminals or an external transformer, a minimum 10 VA is required

STEP 9: Connecting to the Humidifier

Strip the wires used for all the humidifier control terminal connections 1/4".

If furnace accessory terminals are used, wire the solenoid valve directly to the “Out” terminals on the humidifier con- trol. Also attach a jumper wire to the Wire Connector, as shown in Figures 6 and 7. Do not use a Model A50 relay.

NOTE: See the furnace manual for operation of accessory terminals.

If an external transformer is used, connect a Model A50 relay in series with the solenoid valve and the “Out” terminals on the humidifier control. This will allow the humidifier to operate only when the furnace blower is on. (See Figure 6-8 to determine the correct wiring for your model humidifier).

 

 

Figure 7

Figure 6

 

 

 

 

 

 

 

 

MODELS

MODELS

 

2000

60

 

2001

2002

 

55

 

 

 

 

 

 

Figure 8

MODELS

45

86

90

190

Page 3
Image 3
Skuttle Indoor Air Quality Products SEH-7100-000 installation instructions Connecting to the Humidifier