® Modular Boiler Submittal Data
LDWO SERIES—Oil-fired/Hot Water
A Caravan modular boiler system consists of two or more compact
For additional information, see Caravan Engineering Manual, pub.
Standard Equipment |
|
|
|
|
| ||
One per module unless otherwise noted |
| ||
| |||
with |
| ||
| |||
Flame retention oil burner, with nozzle; |
| ||
cadmium sulfide flame detector |
| ||
| |||
Primary burner control |
| ||
System pressure and temperature gauge | Control header (unmounted, | ||
(unmounted) | one per system) | ||
Module pressure and temperature gauge | Flue brush | ||
Module pressure relief valve (ASME) | Module drain cock | ||
(unmounted) Specify 30, 50 or 100 psi. | (unmounted) | ||
Draft regulator (unmounted) |
|
Ratings
Optional Equipment
Hot water supply and return header assemblies
Control panel with automatic lead lag
Oil Caravan ratings/hot water models — LDWO Series
|
| I=B=R | I=B=R Ratings |
|
| I=B=R |
|
|
| Recom- | ||
|
| Firing |
|
|
|
|
| |||||
|
|
| (MBH) |
|
|
|
|
| ||||
|
| Rate |
|
| EDR | Net | Boiler | Water |
| mended | ||
| No. of | #2 Oil |
|
| Gross |
| Water † | Output‡ | Horse- | Content | Ship | Header |
Model No. | Modules | GPH* | Input |
| Output |
| (Sq. Ft.) | (MBH) | power | (gal.) | Wt. | Size § |
2 | 4.30 | 602 |
| 500 | 2900 | 435 | 14.9 | 31.0 | 1570 | 2" | ||
2 | 5.20 | 728 |
| 596 | 3453 | 518 | 17.8 | 35.6 | 1790 | 2" | ||
2 | 6.00 | 840 |
| 684 | 3967 | 595 | 20.4 | 45.2 | 2000 | 3" | ||
3 | 6.40 | 896 |
| 750 | 4347 | 652 | 22.4 | 46.5 | 2355 | 3" | ||
3 | 7.80 | 1092 |
| 894 | 5180 | 777 | 26.7 | 53.4 | 2685 | 3" | ||
3 | 9.00 | 1260 |
| 1026 | 5947 | 892 | 30.6 | 67.8 | 3000 | 3" | ||
4 | 12.00 | 1680 |
| 1368 | 7933 | 1190 | 40.9 | 90.4 | 4000 | 3" | ||
5 | 15.00 | 2100 |
| 1710 | 9913 | 1487 | 51.1 | 113.0 | 5000 | 3" | ||
6 | 18.00 | 2520 |
| 2052 | 11893 | 1784 | 61.3 | 135.6 | 6000 | 3" | ||
7 | 21.00 | 2940 |
| 2394 | 13880 | 2082 | 71.5 | 158.2 | 7000 | 4" | ||
8 | 24.00 | 3360 |
| 2736 | 15860 | 2379 | 81.7 | 180.8 | 8000 | 4" | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
* Light oil, 140,000 Btuh per gallon.
† Based on 150 Btuh per square foot E.D.R. at 170°F average water temperature.
‡Net ratings are based on a piping and
for installation having unusual piping and
NOTE: For higher capacities, specify any combination of standard Caravan models shown.