Image 1
 ® Modular Boiler Submittal Data

LDWO SERIES—Oil-fired/Hot WaterOne per module unless otherwise notedRatingsOptional Equipment ® Modular Boiler Submittal Data

LDWO SERIES—Oil-fired/Hot Water

A Caravan modular boiler system consists of two or more compact cast-iron boilers that offer significant advantages in terms of installed cost, efficiency and reliability. Caravan systems are based on step-firing just enough modules to meet hot water or space heating demands. LDWO systems are available in 602,000 to multi-million Btuh gross input.

For additional information, see Caravan Engineering Manual, pub. C-30 and Caravan oil application guide, pub. CG-10-HWO.

Standard Equipment

 

 

 

 

 

One per module unless otherwise noted

 

Pre-assembled cast-iron heat exchanger

 

with built-in air separators and insulated jacket

 

Swing-out/removable burner door

 

Flame retention oil burner, with nozzle;

 

cadmium sulfide flame detector

 

Hi-limit control, auto reset

 

Primary burner control

 

System pressure and temperature gauge

Control header (unmounted,

(unmounted)

one per system)

Module pressure and temperature gauge

Flue brush

Module pressure relief valve (ASME)

Module drain cock

(unmounted) Specify 30, 50 or 100 psi.

(unmounted)

Draft regulator (unmounted)

 

Ratings

Optional Equipment

Hot water supply and return header assemblies

Control panel with automatic lead lag

Oil Caravan ratings/hot water models — LDWO Series

 

 

I=B=R

I=B=R Ratings

 

 

I=B=R

 

 

 

Recom-

 

 

Firing

 

 

 

 

 

 

 

 

(MBH)

 

 

 

 

 

 

 

Rate

 

 

EDR

Net

Boiler

Water

 

mended

 

No. of

#2 Oil

 

 

Gross

 

Water †

Output‡

Horse-

Content

Ship

Header

Model No.

Modules

GPH*

Input

 

Output

 

(Sq. Ft.)

(MBH)

power

(gal.)

Wt.

Size §

LDWO-600-2-5

2

4.30

602

 

500

2900

435

14.9

31.0

1570

2"

LDWO-750-2-6

2

5.20

728

 

596

3453

518

17.8

35.6

1790

2"

LDWO-850-2-7

2

6.00

840

 

684

3967

595

20.4

45.2

2000

3"

LDWO-900-3-5

3

6.40

896

 

750

4347

652

22.4

46.5

2355

3"

LDWO-1100-3-6

3

7.80

1092

 

894

5180

777

26.7

53.4

2685

3"

LDWO-1300-3-7

3

9.00

1260

 

1026

5947

892

30.6

67.8

3000

3"

LDWO-1700-4-7

4

12.00

1680

 

1368

7933

1190

40.9

90.4

4000

3"

LDWO-2100-5-7

5

15.00

2100

 

1710

9913

1487

51.1

113.0

5000

3"

LDWO-2500-6-7

6

18.00

2520

 

2052

11893

1784

61.3

135.6

6000

3"

LDWO-2900-7-7

7

21.00

2940

 

2394

13880

2082

71.5

158.2

7000

4"

LDWO-3400-8-7

8

24.00

3360

 

2736

15860

2379

81.7

180.8

8000

4"

 

 

 

 

 

 

 

 

 

 

 

 

 

* Light oil, 140,000 Btuh per gallon.

† Based on 150 Btuh per square foot E.D.R. at 170°F average water temperature.

Net ratings are based on a piping and pick-up allowance of 1.15. Slant/Fin should be consulted before selecting a boiler

for installation having unusual piping and pick-up requirements. § Modules in excess of 8 are piped in parallel to first eight.