® Modular Boiler Submittal Data

LZDF SERIES—Dual Fuel/Steam

A Caravan modular boiler system con- sists of two or more compact boilers that offer significant advantages in terms of installed cost, efficiency and reliability. Caravan systems are based on step-firing just enough modules to meet heating demands. LZDF systems are available in 620,000 to multi-million Btuh gross input. For additional information, see Caravan Engineering Manual, pub. C-30.

Standard Equipment

One per module unless otherwise noted Pre-assembled heat exchanger with

insulated jacket.

Dual fuel gas/oil burner with oil valve, gas regulator, gas valve, flame safeguard with UV scanner and on-off fuel transfer switch (unmounted). Gordon-Piatt burner model #S4.1-GO has intermittent gas pilot to light oil and/or gas main flame.

Module pressure gauge and siphon (unmounted).

System pressure gauge and siphon

(unmounted, one per system).

Module pressure re- lief valve, ASME (unmounted) 15 psi.

Double swing draft regulator (unmounted).

Flue brush.

Drain cock (unmounted). Water level sight glass

(unmounted).

Standard Equipment

Dual fuel changeover thermostat. Internal tankless heaters.

Two-stage fuel pump in place of one- stage fuel pump.

ASME Package—includes:

67 Low water cutoff (one per module) PA404A Pressure control (one per mod.) 67M Low water cutoff (one per system) L4079B Manual reset pressure

Ratings

Dual Fuel Caravan ratings and dimensions/steam models–LZDF Series

 

 

 

 

RATINGS FOR GAS

 

 

 

 

RATINGS FOR OIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.

 

 

I=B=R

 

 

 

 

 

I=B=R

 

 

 

Boiler

 

Recom-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of

 

Gross

 

Net

Sq. Ft.

 

Firing

 

Gross

 

Net

Sq. Ft.

 

Water

Weight

mended

 

Htg.

Input

Output

Comb.

Output

Steam

Horse-

Rate

Input

Output

Comb.

Output

Steam

Horse-

Content

with

Header

Model No.

Mods

MPH

MPH

Efficiency

MPH

power

GPH*

MPH

MPH

Efficiency

MPH

power

(gal)

Water

Size

LZDF-600-2-5

2

620

500

83.30

375

1563

14.9

4.30

602

500

85.90

375

1563

14.9

21.4

1506

3"

LZDF-750-2-6

2

750

592

83.20

444

1850

17.7

5.20

728

592

85.80

444

1850

17.7

25.2

1710

3"

LZDF-850-2-7

2

798

620

82.90

466

1946

18.6

6.00

840

674

85.50

506

2108

20.1

29.0

1918

3"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LZDF-900-3-5

3

930

750

83.30

563

2346

22.4

6.40

896

750

85.90

563

2346

22.4

32.1

2259

3"

LZDF-1100-3-6

3

1125

888

83.20

666

2775

26.5

7.80

1092

888

85.80

666

2775

26.5

37.8

2565

5"

LZDF-1300-3-7

3

1197

930

82.90

699

2917

27.9

9.00

1260

1011

85.50

758

3158

30.2

43.5

2876

5"

LZDF-1700-4-7

4

1596

1240

82.90

932

3888

37.2

12.00

1680

1348

85.50

1018

4242

40.3

58.0

3834

6"

LZDF-2100-5-7

5

1995

1550

82.90

1165

4963

46.5

15.00

2100

1685

85.50

1298

5408

50.3

72.5

4794

6"

*Light oil, 140,000 Btu per gallon.

Net ratings are based on piping and pick-up allowance of 1.33. Slant/Fin should be consulted before selecting a boiler for installation having unusual piping and/or pick-up requirements. For higher elevations, input may need to be reduced.

Based on 150 Btuh per square foot E.D.R. at 170°F average water temperature.

§Modules in excess of 8 are piped in parallel in two or more banks.

Page 1
Image 1
Slant/Fin LZDF series dimensions Modular Boiler Submittal Data, Lzdf SERIES-Dual Fuel/Steam, Standard Equipment, Ratings