Slant/Fin SE-140, SE-105, SE-210, SE-70 dimensions Ratings Chart - Gas Boilers, Sentinel Se Series

Models: SE-245 SE-70 SE-210 SE-140 SE-105

1 1
Download 1 pages 49.16 Kb
Page 1
Image 1
RATINGS CHART – GAS BOILERS

RATINGS CHART – GAS BOILERS

®

SENTINEL SE SERIES

Natural and L.P. Propane Gas

 

 

 

NET

 

EFFICIENCY

 

DIMENSIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

(A.F.U.E.)

 

 

 

 

 

 

 

I=B=R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A.G.A.

D.O.E.

RATING

 

 

 

 

 

 

 

MODEL

INPUT

CAPACITY

WATER

WATER

STANDING

INTERMITTENT

A

B

C

D

NUMBER †

(Btuh)

(Btuh)

(Btuh) *

(Sq.Ft.)

PILOT

IGNITION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SE-70

70,000

58,000

50,000

333

81.5

82.0

1118"

1758"

4"

4512"

SE-105

105,000

87,000

76,000

507

81.6

82.1

1418"

2058"

5"

46316"

SE-140

140,000

116,000

101,000

673

81.7

82.2

1718"

2358"

5"

46316"

SE-175

175,000

145,000

126,000

840

81.7

82.2

2018"

2658"

6"

47"

SE-210

210,000

173,000

150,000

1000

81.8

82.3

2318"

2958"

7"

48316"

SE-245

245,000

202,000

176,000

1173

81.8

82.3

2618"

3258"

7"

48316"

*Net ratings are based on a piping and pick-up allowance of 1.15. Slant/Fin should be consulted before selecting a boiler for installation having unusual piping and pick-up requirements. Ratings must be reduced by 4% at 2,000 feet elevation and an additional 4% for every additional 1,000 feet elevation over 2,000 feet.

†Type of gas: after model number, specify gas by name “Natural” or “Propane”.

Note: All Sentinel boilers are tested and rated for capacity under the U.S. Dept. of Energy (D.O.E.) Test Procedure for boilers.

SLANT/FIN CORPORATION, Greenvale, NY 11548 • Phone: (516) 484-2600

FAX: (516) 484-5921In Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario

www.slantfin.com

©Slant/Fin Corp. 2007