HIGH PERFORMANCE HEATING FOR HARD TO HEAT AREAS

Design features help ensure long life and reliable operation.

11

8

7

9

 

 

 

5

4

 

 

6

 

 

 

2

10

3

1 2

12

13

1High performance manifold-type heat exchanger.

2Two built-in air vent tappings. Coin or screwdriver access.

3Brazed tube joints resist rigors of installation and years of operation.

41/2" hot water supply and return fittings.

5Aluminum turbo fin heat exchanger maximizes heat transfer.

6Expanded copper tube bonds fin to copper for high heat transfer.

7Heavier duty 2-speed blower motor for extended life. Internally cooled. Permanently lubricated.

8Tangential aluminum blower.

9Aquastat permits blower operation only when the water temperature is above 130°F.

10Three-position blower switch is easily accessible.

11Hot dipped galvanized chassis resists rust and corrosion.

12Rubber grommets cushion chassis for quiet operation.

1322" matte black grille separates heated air from intake air for better performance.

 

 

Water

HOT WATER RATINGS (BTUH)

 

 

Flow

 

 

 

 

 

Model

CFM

GPM

140°

160°

180°

200°

220°

TK-90

 

3

5154

6958

8715

10465

12216

With SMK or RMK

81

2

4894

6660

8390

10111

11839

Wall Mount Kit

 

1

4005

5616

7227

8839

10450

TK-90

 

3

4437

5914

7350

8770

10218

Kickspace

68

2

4250

5698

7118

8519

9941

 

 

1

3584

4925

6266

7607

8948

TK-70

 

3

4269

5456

6632

7805

8979

With SMK or RMK

72

2

4094

5285

6428

7576

8722

Wall Mount Kit

 

1

3658

4753

5849

6944

8039

TK-70

 

3

3721

4684

5638

6601

7558

Kickspace

60

2

3616

4559

5501

6440

7386

 

 

1

3267

4171

5075

5979

6883

Kickspace Locations No separate kit required

WATER PRESSURE

DROP (FEET W.C.)

 

Models

GPM

TK-90

TK-70

 

 

 

1

0.32

0.34

2

1.30

1.40

3

2.80

3.00

 

 

 

3 YEAR LIMITED WARRANTY

The Kicker comes with a 3-year limited warranty against defects in materials and workmanship. Complete warranty details available upon request.

Ratings are BTU per hour with 65° entering air. Blower motor voltage:

120 VAC, 60 Hz. TK-90---0.72 F.L.A., 41 Watts TK-70---0.62 F.L.A., 37 Watts

1538"

 

17116

 

 

4"

2414"

 

251516"

 

 

 

Recessed Wall Mounted

Surface Wall Mounted

Requires Kit RMK

Requires Kit SMK

©Slant/Fin Corp. 1994. Printed in the U.S.A. 101. Publication No. TK-10.

SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600

FAX: (516) 484-5921Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario

www.slantfin.com

Page 2
Image 2
Slant/Fin TK-70, TK-90 High Performance Heating for Hard to Heat Areas, Year Limited Warranty, HOT Water Ratings Btuh, Gpm