GV100W BOILER
INSTALLATION & OPERATING INSTRUCTIONS
TABLE 3 Maximum Gas Pipe Capacity in ft3/hr
Nominal Iron |
|
| Pipe length |
|
|
| |||
Pipe Size | 10' | 20' | 30' | 40' | 50' | 60' | 80' | 100' | 150' |
|
|
|
|
|
|
|
|
|
|
3⁄4" | 278 | 190 | 152 | 130 | 115 | 105 | 90 | 79 | 64 |
1" | 520 | 350 | 285 | 245 | 215 | 195 | 170 | 150 | 120 |
11⁄4" | 1050 | 730 | 590 | 500 | 440 | 400 | 350 | 305 | 250 |
11⁄2" | 1600 | 1100 | 890 | 760 | 670 | 610 | 530 | 460 | 380 |
|
|
|
|
|
|
|
|
|
|
Note: Maximum pipe capacity in ft3/hr based on 0.60 specific gravity gas at pressures of 0.5 psig or less and a 0.3 " WC pressure drop.
TABLE 4 Equivalent Pipe Length Chart
Equivalent length of pipe fittings in feet
Nominal Iron |
| Type of Pipe Fitting |
| |
Pipe Size | 90° Elbow | Tee | Gate Valve | Gas Cocks |
|
| (branch flow) | (full port) |
|
3⁄4" | 2.06 | 4.12 | 0.48 | 1.25 |
1" | 2.62 | 5.24 | 0.61 | 1.60 |
11⁄4" | 3.45 | 6.90 | 0.81 | 2.15 |
11⁄2" | 4.02 | 8.04 | 0.94 | 2.50 |
|
|
|
|
|
ELECTRICAL WIRING
Electrical Power Connections
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation!
ATTENTION: Au moment de l’entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de câblage peuvent entraîner un fonctionnement
The electrical connections to this boiler must be made in accordance with all applicable local codes and the latest edition of the National Electrical Code,
Line voltage field wiring of controls and other devices must conform to the temperature limitation of type T wire at 95°F, 35°C, above room temperature. Use copper conductors with a minimum size of #14 awg. Low voltage wiring must not be less than #18 awg with a neoprene, thermoplastic or other equivalent insulation having a minimum insulation thickness of 0.012 in, 0.3 mm.
THERMOSTAT INSTALLATION
Always follow the instructions included with the thermostat to be used to control the boiler. Proper location of the thermostat will ensure efficient
CO DETECTORS
WARNING: Installers must follow local regulations with respect to the installation of CO detectors and follow the manufacturer’s stated maintenance schedule for this boiler!
ATTENTION: Observer les règlements règional à l'egard des détecteurs de monoxyde de carbone et observer entretien de manufacturier pour cette chaudière!