TABLE 3 Maximum Gas Pipe Capacity in ft3/hr

Page 13

Page 13

GV100W BOILER

INSTALLATION & OPERATING INSTRUCTIONS

TABLE 3 Maximum Gas Pipe Capacity in ft3/hr

Nominal Iron

 

 

Pipe length

 

 

 

Pipe Size

10'

20'

30'

40'

50'

60'

80'

100'

150'

 

 

 

 

 

 

 

 

 

 

3⁄4"

278

190

152

130

115

105

90

79

64

1"

520

350

285

245

215

195

170

150

120

11⁄4"

1050

730

590

500

440

400

350

305

250

11⁄2"

1600

1100

890

760

670

610

530

460

380

 

 

 

 

 

 

 

 

 

 

Note: Maximum pipe capacity in ft3/hr based on 0.60 specific gravity gas at pressures of 0.5 psig or less and a 0.3 " WC pressure drop.

TABLE 4 Equivalent Pipe Length Chart

Equivalent length of pipe fittings in feet

Nominal Iron

 

Type of Pipe Fitting

 

Pipe Size

90° Elbow

Tee

Gate Valve

Gas Cocks

 

 

(branch flow)

(full port)

 

3⁄4"

2.06

4.12

0.48

1.25

1"

2.62

5.24

0.61

1.60

11⁄4"

3.45

6.90

0.81

2.15

11⁄2"

4.02

8.04

0.94

2.50

 

 

 

 

 

ELECTRICAL WIRING

Electrical Power Connections

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation!

ATTENTION: Au moment de l’entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de câblage peuvent entraîner un fonctionnement in-adéquat et dangereux. S’assurer que l’appareil fonc-tionne adéquatement une fois l’entretirn terminé.

The electrical connections to this boiler must be made in accordance with all applicable local codes and the latest edition of the National Electrical Code, ANSI/NFPA-70. Installation should also conform with CSA C22.1 Canadian Electrical Code Part I if installed in Canada. Install a separate 120 volt 15 amp circuit for the boiler. A shut-off switch should be located at the boiler. The boilermust be grounded in accordance with the authority having jurisdiction, or if none, the latest edition of the National Electrical Code, ANSI/NFPA-70.

Line voltage field wiring of controls and other devices must conform to the temperature limitation of type T wire at 95°F, 35°C, above room temperature. Use copper conductors with a minimum size of #14 awg. Low voltage wiring must not be less than #18 awg with a neoprene, thermoplastic or other equivalent insulation having a minimum insulation thickness of 0.012 in, 0.3 mm.

THERMOSTAT INSTALLATION

Always follow the instructions included with the thermostat to be used to control the boiler. Proper location of the thermostat will ensure efficient trouble-free operation of the boiler. Mount the thermostat to an inside wall at a height approximately five feet above the floor. Avoid placing the thermostat in areas that will not provide an accurate measurement of the room temperature. Locating the thermostat behind a door, in an alcove, close to a source of thermal radiation or in a drafty area will cause poor or sporadic heating.

CO DETECTORS

WARNING: Installers must follow local regulations with respect to the installation of CO detectors and follow the manufacturer’s stated maintenance schedule for this boiler!

ATTENTION: Observer les règlements règional à l'egard des détecteurs de monoxyde de carbone et observer entretien de manufacturier pour cette chaudière!

Page 13
Image 13
Smith Cast Iron Boilers GVIOM-5R GV100W BOILER, Installation & Operating Instructions, Electrical Wiring, Co Detectors