VENTING INSTALLATION
VSP HOOD SYSTEM: Purchased through Southern Pride
VSP HOODS are U/L Listed to the applicable
Southern Pride oven models and are NSF Certified.
HOOD SYSTEM TO INCLUDE:
2
4
3SPECIFY ROOF PITCH
1. Ventilation Hood | 6 | |
2. Two speed fan (1380/2000) | ||
3. | Curb with vented extension and hinge kit | |
| (Specify roof pitch) | 1 |
4. | Grease capture trough |
|
5. | Combustion chamber flue vent |
|
SUPPLIED BY CUSTOMER: | ||
6. Duct from hood to fan | optional VSP Vent Hood System. | |
|
NOTE: If you have a duct longer than 10 feet or an elbow in your duct your installation, it may require a larger capacity exhaust fan. Please specify your duct requirements when ordering the VSP Hood System.
5
ALL MODELS MAY ALSO BE INSTALLED UNDER A CANOPY HOOD RATED
FOR COMMERCIAL COOKING APPLIANCES.
NOTE: THE SIX INCH ALL FUEL CHIMNEY SHOULD EXTEND ATLEAST 3’ ABOVE THE HIGHEST SIDE OF THE ROOF OPENING AND BE AT LEAST 2’ HIGHER THAN ANY PORTION OF THE BUILDING WITHIN 10’. HORIZON TAL.
6” ALL
FUEL CHIMNEY
EXHAUST
FAN
NOTE: THE 10” ALL
FUEL SMOKE EX-
TRACTOR CHIMNEY
TERMIN ATES AT
THE ROOF CURB
10” ALL FUEL SMOKE
EXTRACTOR CH IMNEY
RAIN C AP
THROUGH THE WALL -
DIRECT VENT INSTALLATION
NOTE 1. When installing an Oven through a wall constructed of combustible material, use the Southern Pride Insulation Kit between the oven and the wall.
2.The room that the face of the oven is installed into should have a balanced or positive air pressure. If the room has negative air pressure, smoke could escape into the room during operation.
SUPPLIED BY SOUTHERN PRIDE: (*)
Smoke Extractor Damper with 10” chimney adapter plate
SUPPLIED BY CUSTOMER:
6” All Fuel Chimney, 6” Rain Cap, and all accessories necessary for installation of the 6” chimney.
10” All Fuel Chimney, Exhaust Fan (NOTE: Fan must be listed for use as a commercial kitchen ventilator), fan curb, and all accessories necessary for installation of the smoke extractor system.
The oven’s minimum clearances from combustible materials are 18" on left side, 24" on right, 18" on top, 48" from front, and 2" on back. Minimum clearances are 18" to chimney connector and to smoke extractor chimney connector. Floor may be constructed of a combustible material. (Note: minimum clearance dimensions are from the oven cabinet, not from component cover.) (If provision is made for access to service, minimum clearance can be reduced to 2" on left side.) May be installed through a combustible wall with zero clearance with BBR kit No. 2099.
ANY VENTILATION SYSTEM MUST BE INSTALLED IN ACCORDANCE WITH LOCAL CODES. CONSULT WITH LOCAL OFFICIALS AND A COMMERCIAL KITCHEN VENTILATION CONTRACTOR PRIOR TO INSTALLATION.