Hub Cover Installation

Hub Cover Installation

Install the hub cover as shown in Figure 1 and Figure 7. Tighten all hex nuts to 15 ft·lbƒ (20 N·m) torque.

145

 

300

142

142

144

143

146

 

102

142

 

 

141

Figure 7

Fan Maintenance

Preventative maintenance will prolong useful life and assure contin- ued trouble-free operation. After the first week and subsequently at six month intervals:

Torque all hardware to specifications referenced in this manual.

Visually inspect the fan for airborne debris damage, contact with fan cylinder segments, and corrosive attack. Correct any situations determined detrimental to fan operation.

Remove any accumulated scale or dirt.

Clear blade drain holes.