SBD TANK TYPE HEATERS

SERVICE HANDBOOK

TROUBLESHOOTING THE EFFIKAL DAMPER (continued)

Condition:

Thermostat closed, damper is open fully

STEP 10A

TEST FOR 24VAC BETWEEN BLACK AND YELLOW

IF

THEN

24VAC is present

This is correct – continue to Step 11

24VAC is not present

• See Step 9B.

 

• Check the harness plug connecting.

 

• Check that cam on shaft rotates with

 

shaft.

 

• Replace the damper board.

 

• Ensure that cam is secure against end

 

switch.

Condition:

 

Damper rotates continuously

 

STEP 10B

ADJUST END SWITCH TO CAM CONTACT

IF

THEN

Damper stops in proper position

24 VAC should be open on a call for heat

 

and close during standby/

Damper does not stop in proper position

• Replace damper assembly.

Technical Training Department

30

Ashland City, TN ©2003

Page 31
Image 31
State Industries SBD71 120, SBD85 500 manual Test for 24VAC Between Black and Yellow, Adjust END Switch to CAM Contact