TABLE 4 - OPERATING STATES

 

 

STATE

DESCRIPTION

Standby

The water heater is not in an active heating cycle. This usually indicates the temperature in the tank has reached the

Operating Set Point and the control system has terminated the heating cycle.

 

 

 

Heating

The control system is in the Heating Mode. At least one heating element has been energized.

 

 

Alert

The control system has detected/declared an Alert Condition. The controls system will continue heating operation.

However, a Qualified Service Agent should be contacted to check/service the water heater.

 

 

 

 

The control system has detected/declared a Fault Condition. The control system will discontinue heating operation and

Fault

“lock out.” Power to the water heater must be cycled off and on to reset the control system. Note; cycling power will not

 

reset the control system until the condition that caused the fault has been corrected.

 

TABLE 5 - CONTROL SYSTEM MENUS

 

 

MENUS

DESCRIPTION

Temperatures

Most commonly accessed menu. Operating Set Point, Differential settings, Tank Temperature and Tank Probe

Offset are located in this menu.

 

 

 

Heater Status

Current Operating State/Mode (heating/standby etc) and status (open/closed - on/off - yes/no) of monitored

water heater functions and components are displayed in this menu.

 

 

 

Economy Mode Setup

Seven day 24 hour time clock with temperature set back capability to reduce operating costs during unoccupied

or reduced demand periods.

 

 

 

 

The control system’s CCB (Central Control Board - see wiring diagrams) features on board SPDT (single pole

Alarm Output Setup

double throw) relay contacts for building EMS (Energy Management System) notification of operational conditions

such as Fault Conditions and heating mode status. This menu features a list of user definable conditions for

 

 

relay activation.

Display Settings

Temperature units (°F or °C), appearance (brightness contrast) and backlight delay user adjustable settings are

located in this menu.

 

 

 

Heater Information

Elapsed time of operation, total heating cycle time, heating cycle count, heating element(s) cycle count and on

time along with UIM and CCB software revisions can be viewed in this menu.

 

 

 

Current Fault/Alert

Displays any current Alert or Fault messages.

 

 

 

Retains 9 event history of Fault/Alert messages with time stamp. The Fault History is useful when dealing with

Fault History

intermittent operational problems or when the customer has reset the control system prior to a service agent’s

 

arrival.

 

 

 

Total accumulated number each individual Fault condition has occurred is displayed in this menu. This

Fault Occurrence

running total of Fault Occurrences can be useful in determining which (if any) operational problems have been

 

persistent.

 

 

Restore Factory Defaults

This control system feature allows the user to restore control system user settings to their factory default settings.

 

Alarm Output Setup and Display Settings menu items ARE NOT changed when factory defaults are restored.

 

 

 

Accessible by pressing the corresponding Operational Button from most menus and screen displays. This menu

Help Menu

provides access to instructions and explanations for user settings, Operating States, Status Icons, manufacturer’s

 

web address, technical support phone number and service agent contact information.

 

 

19

Page 19
Image 19
State Industries SSED 5 instruction manual Operating States, Control System Menus, Menus Description

SSED 5 specifications

State Industries, a prominent player in the heating and cooling sector, has unveiled its latest product, the SSED 5 series. This state-of-the-art water heater stands out in the market due to its unique features and advanced technologies designed to enhance efficiency, durability, and user-friendliness.

One of the key characteristics of the SSED 5 series is its innovative design. Constructed using high-quality materials, the unit is built to withstand the rigors of everyday usage while minimizing corrosion and wear. The external casing is both aesthetically pleasing and functional, providing adequate insulation to reduce heat loss, which in turn improves energy efficiency.

Energy-saving technologies are at the forefront of the SSED 5 series. It utilizes advanced heating elements that offer superior performance compared to traditional models. This includes a high thermal efficiency rating, allowing users to enjoy consistent hot water without incurring high utility bills. Moreover, the SSED 5 is equipped with integrated smart technology that enables users to monitor and control the unit remotely via a mobile app. This feature adds convenience and promotes energy conservation by allowing adjustments to be made according to real-time needs.

The SSED 5’s performance is further enhanced by its user-friendly digital control panel. This intuitive interface simplifies operation, allowing users to easily set their preferred water temperature and access diagnostic information. Safety features are also paramount, with built-in mechanisms to prevent overheating and leaks, ensuring peace of mind during operation.

Additionally, the SSED 5 series is notable for its environmental compliance. A commitment to sustainable practices is evident in its low emissions and energy-efficient operation, which contributes to reducing the overall carbon footprint.

In summary, the State Industries SSED 5 series represents a remarkable advancement in water heater technology. With its robust design, energy efficiency, smart technology integration, user-friendly interface, and safety features, it caters to modern consumers looking for reliable and effective heating solutions. As the demand for efficient and environmentally friendly products continues to rise, the SSED 5 is poised to meet and exceed market expectations. This makes it a leading choice for homeowners seeking innovation and quality in their hot water systems.