Figure 1: Pipe Sizing Guide
Pipe Sizing Guide
Pipe Size |
|
|
|
|
|
1/2 | 2 | 2 |
|
|
|
3/4 | 5 | 5 |
|
|
|
1 | 10 | 10 |
|
|
|
1 1/4 | 20 | 20 |
|
|
|
1 1/2 | 30 | 30 |
|
|
|
2 | 50 | 55 |
|
|
|
2 1/2 | 100 | 100 |
|
|
|
3 | 160 | 160 |
|
|
|
4 | 320 | 320 |
|
|
|
6 | 900 | 1000 |
|
|
|
8 | 2000 | 2100 |
|
|
|
10 | 3500 | 3700 |
|
|
|
12 | 5000 | 5800 |
|
|
|
Based on 10’ head loss/100’ of pipe (new pipe) — open piping systems. A safety factor of 15 to 20% should be added based on local conditions.