Figure 3. Wiring diagram for the 2100D and 2100TD detector:

+

INITIATING

LOOP

EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER

UL LISTED

+

COMPATIBLE

CONTROL

 

PANEL

 

RA400Z

REMOTE

ANNUNCIATOR

+

+

 

+

+

–LED

 

RA400Z

 

REMOTE

 

ANNUNCIATOR

OPTIONAL CLASS A WIRING

+

+

+

–LED

A78-2331-02

 

CAUTION

 

or analog voltmeter to check the detector sensitivity as

 

 

 

 

described in the test module’s manual.

Dust covers are an effective way to limit the entry of dust

C. Smoke Entry Test

into smoke detector sensing chambers. However, they may

Hold a smoldering punk stick or cotton wick at the side

not completely prevent airborne dust particles from en-

of the detector and gently blow smoke through the de-

tering the detector. Therefore, System Sensor recommends

tector until the unit alarms.

the removal of detectors before beginning construction or

D. Direct Heat Method (Model 2100TD only – Hair dryer of

other dust producing activity. Be sure to remove dust covers

1000-1500 watts).

from any sensors that were left in place during construction

Direct the heat toward either of the side thermistors.

as part of returning the system to service.

Hold the heat source about 12 inches from the detector

 

 

 

 

Testing

in order to avoid damage to the plastic. The detector will

reset only after it has had sufficient time to cool and the

NOTE: Before testing, notify the proper authorities that the

power source has been momentarily interrupted.

smoke detector system is undergoing maintenance

Both smoke and heat detection testing are recommended

and will temporarily be out of service. Disable the

for verifying system protection capability.

zone or system undergoing maintenance to prevent

 

unwanted alarms.

A detector that fails to activate with any of the above tests

Detectors must be tested after installation and following

should first be cleaned as outlined in the MAINTENANCE

periodic maintenance. Test the 2100D as follows:

section which follows. If the detector still fails to activate, it

A. Test Switch

should be returned for repair.

1. A recessed test switch is located on the detector hous-

 

ing (See Figure 4).

Notify the proper authorities the system is back on line.

2. Push and hold the recessed test switch with a 0.18

 

inch maximum diameter tool such as an allen wrench

Maintenance

or small screwdriver.

NOTE: Before removing the detector, notify the proper

3. The detector’s LED should light within 5 seconds.

authorities that the smoke detector system is un-

B. Test Module (System Sensor Model No. MOD400R).

dergoing maintenance and will temporarily be out

The MOD400R test module can be used with a DMM

of service. Disable the zone or system undergoing

 

 

 

 

 

 

 

 

maintenance to prevent unwanted alarms.

Figure 4. Top and side views showing position of test switch:

LED

 

TEST MODULE

PUSH RECESSED

SOCKET

SWITCH WITH A

RECESSED TEST

SWITCH

0.18MAX. DIAMETER TOOL

D200-54-00

3

I56-710-09

Page 3
Image 3
System Sensor 2100TD, 2100D manual Testing, Maintenance