System Sensor specifications B501BH Terminals, No. Function, Mounting, Wiring Guidelines

Models: B501BH

1 4
Download 4 pages 8.2 Kb
Page 2
Image 2
B501BH Terminals

B501BH Terminals

No. Function

1External Supply Positive (+)

2External Supply Negative (–)

3Negative (–) Comm. Line In and Out

4Positive (+) Comm. Line In and Out

5Sounder Base Interconnect

Terminals 3 and 4 are used for the communication circuit.

Mounting

Mount the B501BH directly to an electrical box, using the mounting kit, supplied (see Figure 2).

The sounder base is 1.1-inches deep. Electrical boxes must be 4-inches square by at least 112 inches deep - 218 inches is recommended.

NOTE: A maximum space of 18 inch from the outside edge of the electrical box to the inside edge of the dry- wall or ceiling tile is allowable.

Wiring Guidelines

All wiring must be installed in compliance with the National Electrical Code and the local codes having juris- diction and must not be of such length or wire size which would cause the base to operate outside of its published specifications. The conductors used to connect smoke sen- sors to control panels and accessory devices should be color coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from respond- ing properly in the event of a fire.

For signal wiring (the wiring between interconnected sen- sors or modules), it is recommended that the wire be no smaller than 18 gauge (1.0 square mm). Wire sizes up to 12 gauge (2.5 square mm) may be used with the base. For best system performance, the power (+ and –) wires and the communication circuit wires should be twisted pair or shielded cable installed in separate grounded conduit to protect the communication loop from electrical interfer- ence.

Make wire connections by stripping about 38" of insulation from the end of the wire. Then, slide the bare end of the wire under the clamping plate, and tighten the clamping plate screw. Do NOT loop the wire under the clamping plate (See Figure 3).

The zone wiring of the sensor base should be checked before the sensor heads are installed. Check the wiring for continuity and polarity in the base.

See the individual sensor manual for the maximum sensor installation temperature.

Figure 1. Terminal layout:

Figure 2. Mounting:

Figure 3:

MOUNT B501BH

TO ELECTRICAL BOX

4 INCH SQUARE BOX

A78-1993-02

D650-03-00

2

I56-491-06R

Page 2