G. BURNER SPECIFICATIONS AND APPLICATIONS

All installations and services must be performed by qualified service personnel.

G. BURNER SPECIFICATIONS AND APPLICATIONS

FURNACE

THERMO

*

BECKETT

HEAD

STATIC

MODEL

PRIDE’S

INS

BURNER

 

PLATE

 

BURNER

 

MODEL &

 

 

 

SPEC NO.

 

TUBE

 

 

 

 

 

LENGTH

 

 

OH6FA072D**B

TP2501

N

AFG-4.5”

F3

3-3/8

 

 

 

 

 

 

MAXIMUM NOZZLE SIZE**

0.75X80° H

SHIPPED

OIL

NOZZLE

PUMP

SIZE

PRESSURE

 

(PSIG)

 

 

0.60X80° H

120

 

 

The optional BF3 Riello flame retention oil burner can be used with OH6.

FURNACE

 

THERMO

*

RIELLO

HEAD

STATIC

MAXIMUM

SHIPPED

OIL

MODEL

 

PRIDE’S

INS

BURNER

 

PLATE

NOZZLE

NOZZLE

PUMP

 

 

BURNER

 

MODEL &

 

 

SIZE**

SIZE

PRESSURE

 

 

SPEC NO.

 

TUBE

 

 

 

 

(PSIG)

 

 

 

 

LENGTH

 

 

 

 

 

OH6FA072D**R

 

C8511325

S

BF3-4.5”

N/A

N/A

0.70X80° H

0.60X80° H

140

 

 

 

 

 

 

 

 

 

 

* INSULATOR

S = SLEEVE

OR

N = NONE

 

 

 

 

 

THE NOZZLE SIZE GIVES THE NOMINAL FLOWRATE, IN GPH, FOLLOWED BY THE SPRAY ANGLE, IN DEGREE’S, AND THE SPRAY PATTERN, EITHER “H” FOR HOLLOW CONE OR “S” FOR SOLID CONE. FOR EXAMPLE, A NOZZLE RATED AT 0.65 GPH @ 100 PSIG THAT PROVIDES AN 80° SPRAY ANGLE AND A HOLLOW SPRAY PATTERN WOULD BE ABBREVIATED IN THE TABLE AS “0.65 X 80°H”.

For more specific burner information, contact Thermo Products, LLC. P.O. Box 217, North Judson, IN 46366. Phone 574-896-2133.

OIL NOZZLE CAPACITY CHART

 

NOZZLE SIZE

EQUIVALENT HEAT

EFFECTIVE HEATING

UNITS

(GPH)

 

INPUT RATE*

CAPACITY**

 

 

(BTU/HR)

(BTU/HR)

Beckett

Riello

 

 

 

 

 

 

 

 

 

OH6FA060D***

.50

.50

70,000

60,000

OH6FA072D***

.60

.60

85,000

73,000

OH6FA090D***

.75

.70

106,250

90,000

All rates shown achieved with 120 PSIG pump pressure for Beckett and 140 PSIG pump pressure for Riello.

*Based on #2 domestic heating fuel oil having heating value of 140,000 BTU per gallon.

**Based on thermal efficiency of 84%-85%.