TABULAR DATA SHEET

TABULAR DATA SHEET

Outdoor Split System Heat Pump 1.5 Thru 5 Tons

MODELS: THJF18* THRU 60 14.5 SEER – R-410A, 1 PHASE

Physical and Electrical Data

MODEL

 

THJF18

THJF24

THJF30

 

THJF36

 

THJF42

THJF48

THJF60

 

S41S3

S41S3

S41S3

 

S41S3

 

S41S3

S41S3

S41S3

 

 

 

 

Unit Supply Voltage

 

 

 

 

208-230V, 1 60Hz

 

 

 

Normal Voltage Range 1

 

 

 

 

187 to 252

 

 

 

Minimum Circuit Ampacity

11.9

17.6

17.3

 

23.7

 

26.1

28.8

35.3

Max. Overcurrent Device Amps 2

20

30

30

 

40

 

45

50

60

Min. Overcurrent Device Amps 3

15

20

20

 

25

 

30

30

40

Compressor Type

 

Scroll

Scroll

Scroll

 

Scroll

 

Scroll

Scroll

2-Stage Scroll

Compressor

Rated Load

9.0

13.4

12.8

 

17.9

 

19.8

28.8

35.3

Amps

Locked Rotor

48.0

58.3

64.0

 

96.7

 

115.0

115.0

118.0

Crankcase Heater

 

No

No

No

 

No

 

No

No

No

Factory External Discharge Muffler

Yes

Yes

Yes

 

Yes

 

Yes

Yes

Yes

Factory External Check Valve

No

No

No

 

No

 

No

No

No

HS Kit Required with TXV 4

No

No

No

 

No

 

No

No

No

Fan Motor Amps

Rated Load

0.7

0.8

1.3

 

1.3

 

1.3

1.3

1.3

Fan Diameter Inches

 

24

22

24

 

24

 

24

24

24

 

Rated HP

1/10

1/8

1/4

 

1/4

 

1/4

1/4

1/4

Fan Motor

Nominal RPM

825

1075

850

 

850

 

850

850

850

 

Nominal CFM

2000

2000

3900

 

3900

 

3900

3800

3800

 

Face Area Sq. Ft.

15.72

19.17

23.58

 

23.58

 

23.58

23.58

23.58

Coil

Rows Deep

1

1

1

 

1

 

1

2

2

 

Fin / Inches

22

22

22

 

22

 

22

18

18

Liquid Line Set OD (Field Installed)

3/8

3/8

3/8

 

3/8

 

3/8

3/8

3/8

Vapor Line Set OD (Field Installed)

3/4

3/4

3/4

 

3/4

 

7/8

7/8

1-1/8

Unit Charge (Lbs. - Oz.) 5

6 - 15

7 - 14

9 - 14

 

10 - 9

 

10 - 14

14 - 2

14 - 2

Charge Per Foot, Oz.

 

0.62

0.62

0.62

 

0.62

 

0.67

0.67

0.75

Operating Weight Lbs.

145

145

176

 

193

 

198

248

290

1.Rated in accordance with ANSI/AHRI Standard 110-2002, utilization range “A”.

2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.

3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.

4.See Hard Start Kit Accessory Installation Manual for Hard Start Kit part number for each model.

5.The Unit Charge is correct for the outdoor unit, matched indoor coil, and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

All dimensions are in inches. They are subject to change without notice.

Certified dimensions will be provided upon request.

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

Dimensions

 

Refrigerant Connection

 

 

 

 

 

(Inches)

 

Service Valve Size

 

 

 

Model

A1

 

B

 

C

Liquid

Vapor

 

 

 

 

 

 

 

 

 

18

28

 

34

 

34

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

24

40

 

29

 

29

 

3/4”

 

 

 

 

 

 

 

 

 

 

 

 

 

30

40

 

34

 

34

3/8”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

40

 

34

 

34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

42

40

 

34

 

34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

48

40

 

34

 

34

 

7/8”

 

 

 

 

 

 

 

 

 

 

 

 

 

B

60

40

 

34

 

34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Including Fan Guard.

 

 

 

MAC-222

ECN 5287-MA 121005