INSTALLATION

Battery Cable Fusing

A fuse is required by the NEC to protect the battery and cables. A UL Listed DC rated slow blow fuse must be installed in the positive

(+)battery cable, within 18 inches of the battery.

Recommended Fuse: UL Listed Class T

JLLN with a DC Rating. This fuse with fuse holder is available from your dealer or Heart Interface.

COMPRESSION / RING TERMINAL

 

NUT

 

LOCK WASHER

 

FLAT WASHER

INVERTER

BATTERY

CABLE

CABLE

 

 

FUSE

For Freedom 15 & 15D

 

 

200 Amp Fuse & Holder

PN# 84-4155-00 (C/R)*

200 Amp Fuse & Holder

PN# 84-4158-00 (R/R)**

200 Amp Fuse Only

PN# 84-4157-00

 

For Freedom 20 & 20D

 

 

300 Amp Fuse & Holder

PN# 84-4156-00

(C/R)*

300 Amp Fuse & Holder

PN# 84-4154-00

(R/R)**

300 Amp Fuse Only

PN# 84-4151-00

 

*Compression / Ring Terminal

**Ring / Ring Terminal

_

+

+ (red)

EXPLODED VIEW

OF FUSE ASSEMBLY

RING / RING TERMINAL

NUT

LOCK WASHER

FLAT WASHER

INVERTER

CABLE BATTERY CABLE

FUSE HOLDER

FUSE

WARNING

Improper stack up of hardware will cause excessive heat and fuse failure. Stack up as shown.

28

FUSE HOLDER

Part No. 90-0123-00 Libertycombi.p65 10/26/98

Page 28
Image 28
Thomas & Betts 20D, 15D owner manual Battery Cable Fusing, Recommended Fuse UL Listed Class T