
Note: If there is a room above ceiling level, firestop spacer must be installed on the bottom side of the ceiling. If an attic is above ceiling level, firestop spacer must be installed on top side of ceiling joist (Figures 29 and 30).
Room Above
Firestop Spacer
Figure 29
Attic Above
Firestop Spacer
Figure 30
For Canada OnlyWhen installing the chimney system through an open attic space, the attic shield assembly- firestop spacer must be used (Figure 31 ). This installation is Warnock Hersey Inc. listed only for use in Canada.
Open Attic Space
Figure 31
Step 4. Note: Chimney sections are constructed with a unique locking tab design which ensures an immediate, tight assembly between sections. Plan your chimney requirements carefully before assembly as chimney is difficult to disassemble after installation. If disas- sembled, the tabs might become damaged. Be certain tabs are properly formed to ensure tabs engage properly.
The FTF8 chimney system is a
Figure 32
Outer pipe section installs in just the opposite way; the lanced end goes down and each new section goes OVER the outside of the previous section installed (Figure 33 ).
Locking Tabs (Lances)
Figure 33
Note: Assemble one component of chimney at a time (inner section first, then outer section last) beforeproceedingwiththenextcompletesection.
Continue to assemble the chimney up through framed ceiling opening. Assemble just enough to penetrate the roof flashing openings (Figure 34 ). Always maintain 2" (51 mm) minimum air space to combustible materials and always check each pipe joint (inner and outer) to ensure proper engagement.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
2" (51mm) Min. Air Space to Combustibles
Figure 34
Check vertical alignment of chimney pipe so that it projects from the roof in a true vertical position. Security's chimney sections do not need to be screwed together. Additional reinforcement is not necessary, except in certain offset conditions (see to page 16, Figure 47 ).
Step 5. The height of vertical chimney pipe supported only by the fireplace must not exceed 30' (9.1 m). Chimney heights above 30' (9.1 m) must be supported by a Model FTF8- S4 stabilizer installed at 30' (9.1 m) intervals.
Note: The Model
Install the Model
Figure 35
Note: Do not apply excessive pressure to any subsequent chimney sections following the stabilizer when installing. Ensure each subsequent chimney section is securely attached by testing as noted in Step 4.
11