227.11 Troubleshooting
Displayed on LCD Audible Alarm Alarm Description What You Should Do
Output Overload Two Beeps/sec The UPS is overloaded (in
Line Mode). More power
required than the UPS can
provide. The UPS operates
in bypass.
Remove loads from the UPS; least to
most critical. If this solves the
problem, the UPS will return to
normal operation.
Battery Test No Beeps Battery test active. No action needed.
User Notification only.
Over-Charge Constant Beep Overcharged Batteries. Turn off loads. Turn off UPS.
Call service @ 1-877-867-8773
Low Battery 2 Beeps/5 sec UPS operating on Battery
Power and will shut down
soon due to low battery
voltage.
The unit will restart
Automatically when acceptable
power returns.
On-Battery 1 Beep/5 sec UPS operating on Battery
Power. Save your data and perform a
controlled shutdown.
Charger Failure Constant Beep Failed Charger. Call service @ 1-877-867-8773
Over-Temperature Constant Beep High ambient
Temperature. Ensure that the UPS fans and
vents are not blocked, and that
the ambient temp. is < 40° C. If
problem persists call service @
1-877-867-8773
Output Short Constant Beep Output short circuit. Call service @ 1-877-867-8773
High output Voltage Constant Beep High output voltage. Call service @ 1-877-867-8773
Low Output Voltage Constant Beep Low output voltage. Call service @ 1-877-867-8773
Bus Fault 2 Beeps/sec High internal DC bus
Voltage. Turn off loads. Turn off UPS.
Call service @ 1-877-867-8773
Site Wiring Fault 1 Beep/sec Voltage detected between
neutral and ground. UPS main connector wrong
polarity. Rotate the connector
(Schuko-electric contact). UPS
installed to main supply without
ground. See section 5.5 for
information on how to disable
the Site wiring alarm.
Line Abnormal 1 Beep/sec Wrong AC Line backed
up during auto restart.