| Toshiba International Corporation | |
| Uninterruptible Power Systems | |
|
|
|
| Max Peak Current | 45A |
| Overload Capacity | 125% for 30 secs, 150% for 10 secs |
| Crest Factor | 3.0 at full load |
| Frequency | 50/60 Hz Auto Sensing |
| Frequency Regulation | ± 0.5Hz/± 1.0Hz/± 1.5Hz (authorized service center selectable only) |
| Wave Form | Sine wave, Zero Transfer Time |
| Load Power Factor | 0.85 |
| Efficiency AC to AC | Greater than 83% |
| Common Mode Noise | Less than 0.5 Vrms |
BATTERY | DC Voltage | 216V |
| Backup Time | 10 min (full load) 30 min (half load) |
| Battery type | Enersys |
| Number of batteries Pack | 3 (Six batteries in each pack) |
| Recharge time | <12 hours to 90% |
| Interface | |
| Input | Hardwire Input |
| Output | Hardwire Output |
| Dimensions WxDxH (mm) | 838x254x711 |
BATTERY | Ship Dimensions WxDxH (mm) | 965x432x940 |
| Dimensions W x D x H (inch) | 33x10x28 |
| Ship Dimensions WxDxH (inch) | 38x17x37 |
| Weight kg (lb) | 120.2 (265) |
| Ship Weight kg (lb) | 127 (280) |
| External Matching Battery Cabinet | Single - 70 Mins, Double - 140 Mins. Max Two Cabinets. Part #: |
| Line Cord Options | 3.6kVA |
| Receptacles Options | Four |
|
| Five |
|
| Two |
| Network Interface Card | RemotEye II - Part #: |
| Environmental Monitoring Device | Part #: |
ENVIRONMENT | Operating Ambient Temperature | 0 ~ 40oC (32 ~ 104oF) |
| Recommended Temperature | +15oC ~ 25oC |
| Storage Temperature | |
| Humidity | |
| Audible Noise | 50dB (A) maximum @ 1 meter from Front Panel |
UE3G2L036C61T