TOSHIBA G8000 Series UPS

Installation Planning Guide for 150kVA UPS

Standard System: 480V Input, 480Y/277V Output

General Mechanical Information

 

Dimensions

 

 

Weight

 

 

(W x D x H)

 

 

 

 

 

 

 

 

 

Inches

 

Lbs.

 

55.1 x 31.5 x 78.75

2,756

 

Approximate Full-Load

Heat Loss

Btu/Hr

37,914

Primary AC Input (480V 3-Phase / 3-Wire)

Maximum Input Power

Suggested External

Suggested Minimum Feeder

Suggested Maximum Feeder Length

 

Demand

 

Overcurrent Protection

Wire Size Per Phase

For Min. Wire Size in Steel Conduit

kVA

PF

 

Amps

Amps

AWG or kcmil at 75º C Temp. Rating

Feet

150

>0.98

 

180

225 AT

(1) x 4/0

480

Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)

Maximum Input Power

Suggested External

Suggested Minimum Feeder

Suggested Maximum Feeder Length

 

Demand

 

Overcurrent Protection

Wire Size Per Phase / Neutral

For Min. Wire Size in Steel Conduit

kVA

PF

 

Amps

Amps

AWG or kcmil at 75º C Temp. Rating

Feet

150

0.8

 

180

225 AT

(1) x 4/0 / (2) x 3/0

380

Battery Input (360VDC Nominal)

 

Battery Capacity Required

Maximum Discharge

Suggested External

 

Suggested Minimum Feeder

 

 

for Full Load Output

at Full Load Output

Overcurrent Protection

 

Wire Size Per Phase

 

 

kWB

Amps DC

Amps

 

 

 

 

 

AWG or kcmil at 75º C Temp. Rating

127.7

448

500 AT

 

(2) x 4/0

Suggested Maximum Feeder Length For Min. Wire Size in Steel Conduit

Feet

70

AC Output (480/277V 3-Phase / 4-Wire)

 

Rated Output Power

 

 

Suggested External

 

 

Suggested Minimum Feeder

 

 

Suggested Maximum Feeder Length

 

 

 

 

Overcurrent Protection

 

 

Wire Size Per Phase / Neutral

 

 

For Min. Wire Size in Steel Conduit

 

 

 

 

 

 

 

 

 

 

 

 

 

kVA

PF

Amps

 

 

Amps

 

 

AWG or kcmil at 75º C Temp. Rating

 

 

Feet

 

150

0.8

180

 

 

225 AT

 

(1) x 4/0 / (2) x 3/0

380

 

Important Notes:

1.Maximum Current required at Primary AC Input based on full load output and maximum battery charging current.

2.Output load conductors are to be installed in separate conduit from input conductors.

3.Control wires and power wires are to be installed in separate conduits.

4.Recommended AC input and output overcurrent protection based on continuous full load current per NEC.

5.Wiring shall comply with all applicable national and local electrical codes.

6.Grounding conductors to be sized per NEC Article 250-122. Neutral conductors to be sized per NEC Article 310.15.

-Primary AC Input: 3φ, 4-wire + ground.

-Alternate AC Input: 3φ, 4-wire + ground.

-AC Output: 3φ, 4-wire + ground.

-DC Input: 2-wire (Positive/Negative) + ground.

7.Nominal battery voltage based on the use of VRLA type batteries (2.0 volts/cell nominal).

8.Maximum battery discharge current based on lowest permissible discharge voltage of 1.6 VPC.

9.DC wires should be sized to allow not more than a 2-volt drop at maximum discharge current.

10.Weights do not include batteries or other auxiliary equipment external to the UPS.

11.Sizing calculations based on the following assumptions:

-Not more than 3 current-carrying conductors installed in steel conduit in ambient temperature of 30 degrees C.

-Temperature rating of conductors and terminals: 90 deg. C.

-Feeder distance calculations based on NEC Tables 8 and 9 data, allowing for 2% AC voltage drop.

-Reference: 2002 NEC Handbook. Consult latest edition of applicable national and local codes for possible variations.

12.Ratings of wires and overcurrent devices are suggested minimums. Consult with a registered Professional Engineer within your local area for proper size selections.

TOSHIBA INTERNATIONAL CORPORATION

13131 West Little York Road

Houston, TX 77041

Telephone: (800) 231-1412

Fax: (713) 896-5212

Corporate Web Site: www.tic.toshiba.com

Group Web Site: www.toshibaups.com

Rev. 1.03

Page 1 of 1

G8000-IPG-150kVA

Page 1
Image 1
Toshiba dimensions Toshiba G8000 Series UPS, Installation Planning Guide for 150kVA UPS