Toshiba T300MVi Model Range, Power Requirements, Control Specifications Input, Control Interface

Models: T300MVi

1 4
Download 4 pages 2.99 Kb
Page 4
Image 4
MODEL RANGE

POWER REQUIREMENTSCONTROL SPECIFICATIONS INPUT T300MVi

MODEL RANGE

300 to 600 HP

700 to 1000 HP

1250 to 2000 HP

2250 to

3000 to

2500 HP

3500 HP

4000 to 6000 HP

7000 HP*

8000 to 10000 HP*

Voltage Rating

 

 

 

 

 

 

 

 

 

 

 

 

 

4160 VAC

 

 

 

 

 

 

 

 

 

 

Dimensions (H x W x D)

103.7 x 48 x 48 in.

103.7 x 60 x 48 in.

103.7 x 122 x 43.4 in.

103.7 x 164

103.7 x 174

103.7 x 222 x 49.5 in.

103.7 x 307.5

103.7 x 402.5

 

 

 

 

 

 

 

 

 

 

 

 

 

x 49.5 in.

x 49.5 in.

 

 

 

 

 

x 60 in.

 

x 60 in.

Weight

 

6,200 lbs.

 

 

7,600 lbs.

 

12,500 lbs.

16,500 lbs.

19,000 lbs.

 

27,750 lbs.

37,500 lbs.

64,800 lbs.

Current Rating (A):

37

50

62

74

87

99

112

124

155

186

217

248

279

310

372

434

496

558

620

682

744

868

992

1100

1240

Nominal HP** (4160 V)

300

400

500

600

700

800

900

1000

1250

1500

1750

2000

2250

2500

3000

3500

4000

4500

5000

5500

6000

7000

8000

9000

10000

POWER REQUIREMENTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Tolerance

Voltage: ±10%; Frequency: ±5%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main Circuit

Three-Phase 4160 V; Integrated 24-Pulse Copper-Wound Isolation Transformer; Five-Level NPC Medium Voltage IGBT Output

 

 

Control Circuit

Integral to Main Transformer; Includes 460 V & PT for 120 V Control

 

 

 

 

 

 

 

 

 

 

 

Output Frequency

0 to 120 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL SPECIFICATIONS INPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control Method

Five-Level Pulse-Width Modulation (PWM) Output Control with Neutral-Point Clamping (NPC)

 

 

 

 

V/Hz Control

V/Hz, Sensorless Vector Control, Variable Torque, Closed-Loop Vector Control, & Constant Torque (Optional)

 

 

 

 

PWM Carrier Frequency

Fixed at 2 kHz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency Setting

4 to 20 mA, 0 to 10 VDC Serial Communication Input, & Rotary Encoder Integrated into EOI

 

 

 

 

Speed Regulation

Open Loop: Up to 0.5%; Closed Loop: Up to 0.1%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main Protective Functions

Current Limit, Overcurrent, Overload, Undervoltage, Overvoltage, Ground Fault, CPU Error, & Soft Stall

Overload Current Rating

 

100% Continuous; 115% for One Minute Every 20 Minutes (1000, 2000, & 6000 HP at 110%)

CONTROL INTERFACE

 

 

 

Digital Input

 

Eight Discrete Input Terminals with Programmable Functions

Digital Output

 

Six Available Digital Programmable Outputs (One Used Internal to Drive)

Analog Input

 

Two Selectable Currents (0/4 to 20 mA) or Voltage (0 to 10 VDC) Input Signals

Analog Output

 

Eight Selectable Currents (0/4 to 20 mA) or Voltage (0 to 10 VDC) Output Signals with Programmable Function

Communication Ports

 

Profibus, Modbus RTU, Modbus, TCP/IP, TOSLINE-S20, & DeviceNet

SAFETY FEATURES

 

Standard Pad-Lockable Input Fuse Disconnect Switch with Vacuum Contactor, Interlocked Doors, & Viewing Window

ELECTRONIC OPERATOR INTERFACE (EOI)

 

 

Display

 

6-Line x 20-Character Graphical Plain-English Back-Lit LCD Display for Programming, Monitoring, & Diagnostics

 

 

 

LED Indicators

 

Run (Red)/Stop (Green) & Local (Green)

Keys

 

Local/Remote, Enter, Mon/Prg, Esc, Run, & Stop/Reset

 

 

 

Monitoring

Frequency Command Screen; Multiple Parameters Displayed: Motor Current, Motor Speed, Motor Voltage, DC Voltage, Input Voltage, Output Voltage, Run Time, Output Power, Motor kW, Motor kWH, Motor kVAH, Motor kVAR, & On-Time Control Power

CONSTRUCTION

Enclosure

ANSI-61 Gray; NEMA 1 Ventilated, & IP20 Per IEC-60529; Gasket & Filter; Free-Standing; Front-Access Only

Power Cables

Top/Bottom Access for Input/Motor Cables

Cooling

Forced-Air Cooled (Redundant Fan Option)

Standards & Compliances

NEC, NEMA, UL, ULC, ANSI, & American Recovery & Reinvestment Act Compliant

AMBIENT CONDITIONS

 

 

Ambient Temperature

0 to 40°C (50°C Option Available)

Altitude

3,281 ft. Above Sea Level (Up to 14,764 ft. Option Available)

Humidity

95% Maximum (Non-Condensing)

Installation

Indoor; No Direct Sunlight; Protect from Corrosive Gases

 

All Information Subject to Change

 

*Models Not UL Listed

 

**Typical HP Rating of a 4-Pole Motor; Contact Factory for Applications on Constant Torque Loads

TOSHIBA INDUSTRIAL PRODUCTS:

• Adjustable Speed Drives

• Motors

 

• Motor Controls

 

• Instrumentation & PLCs

www.toshiba.com/ind

• Uninterruptible Power Systems

© 2012 Toshiba International Corporation • Industrial Division • 13131 West Little York Road • Houston, Texas 77041 USA • Tel +713-466-0277 US 1-800-231-1412 • Rev. 120221

Page 4
Image 4
Toshiba T300MVi Model Range, Power Requirements, Control Specifications Input, Control Interface, Safety Features, Motors