Flushing/Purging Units with ClimaDry
Units equipped with ClimaDry must be flushed/purged with a flush cart. Detailed general flushing /purging instruction can be found in the Flow Controller III IOM.
The unit must be powered (but not operating) during flushing/purging. Unit power is required to operate the
When flushing/purging units equipped with ClimaDry the earth loop should be fully flushed/purged before attempting to flush/purge the heat pump. Once the earth loop is flushed, position the flushing valves to flush the heat pump. Then with flushing flow
Energize the modulating
Note, if the ClimaDry sensor, located in the supply air stream is above 70°F it must be disabled to allow the modulating valve to shift. Disable this sensor by removing the white wire from the Low Voltage Terminal Block (LVTB) shown in figure 1.
Figure 1. Flushing/Purging Wiring
White Thermistor Wire | Red |
Under extreme circumstances this procedure may be required multiple times to purge all air from the circuit. After completing the flushing/purging procedure, restore the red wire to the ACC1 ‘N.O.’ terminal on the DXM for normal operation. Return the white sensor wire to the LVTB, if it was removed, as shown in figure 2.
White Thermistor Wire | Red |
Figure 2. Normal Unit Wiring
Extra care must be taken when using
ClimaDry Whole House Dehumidification - ClimateMaster Geothermal Heat Pumps - Rev.: 18 April, 2008B
13