Standard Features
Soft Start - Voltage Ramp/Current Limit Soft Stop - Decel/Pump Control Current Ratings: 6 - 1250A
Voltage Ratings: 208 - 600V
Continuous Rating - 125%
Overload Capacity - 500% for 60 seconds Overload Capacity - 600% for 30 seconds 120Vac Control Voltage (240Vac Optional) UL & cUL Listed
Protective Features
TS Series (6 - 32A): Overtemperature & Overload
TD Series (48 - 1250A): Overtemperature, Electronic Overload (Class 5 - 30), Undercurrent (10 - 90% of motor FLA), Shorted Load, Shorted SCR (Shunt trip - separate trip relay), Overcurrent (50 - 300% of motor FLA), Phase Loss/Imbalance (5 - 30%), Repetitive Starting
TX Series (48 - 1250A): Overtemperature, Electronic Overload (Class 5 - 30), Undercurrent (10 - 90% of motor FLA), Shorted Load, Shorted SCR (Shunt trip - separate trip relay), Overcurrent (50 - 300% of motor FLA), Line Frequency, Phase Loss, Current Imbalance (5 - 30%), Phase Reversal, Repetitive Starting, Ground Fault, Overvoltage, Undervoltage, and optional Stator & Bearing RTD inputs
Adjustments
Status Indicators
Control "Power On"
Full Voltage "At Speed"
Shunt Trip
Shorted SCR
Over Current
Phase Loss
Over Temperature
Overload
Digital TD Series
Operator Interface Panel
with 4 Digit Display & 8 Function Keys
TS Series:
Voltage Ramp Start (0 - 60 seconds) Initial Voltage Adjustment (0 - 80%) Current Limit Start (200 - 500%)
Soft Stop - Adjustable Deceleration (0 - 30 sec.) Stop Voltage Adjustment (0 - 100%)
TD & TX Series:
Voltage Ramp Start (1 - 120 seconds) Initial Voltage Adjustment (0 - 100%) Current Limit Start (200 - 600%)
Soft Stop - Adjustable Deceleration (1 - 60 sec.) Stop Voltage Adjustment (0 - 100%)
Beginning Decel Voltage Level (0 - 100%) Voltage Jog
Kick Start (10 - 100% Voltage, 0.1 - 2 sec.) Starts per Hour (1 - 10 Starts/hr, 1 - 60 min.
between start attempts)
Coast Down Lockout Timer (1 - 60 min.) Overload Reset (Manual or Automatic)
Metering/Communications
TD Series:
Phase Currents, Remaining Thermal Capacity,
Elapsed Time (ETM), Run Counter, Fault
Codes, Fault History, Lockout Time Remaining,
Real Time Clock.
Communications: Modbus RTU, RS485
TX Series:
Phase Currents (A, B, C), Ground Current, Avg. Current, Unbalance %, RPM, Line Freq., Power Factor, kVAR, kW, kVA, kW Demand, kVAR Demand, kWH, Remaining Thermal Capacity, Required Thermal Capacity to Start, RTD Data (12 RTDs), Elapsed Time (ETM), Run Counter, Fault History, Lockout Time Remaining, Real Time Clock, plus more.
Communications: Modbus RTU, RS485 or RS422
TX Series
Operator Interface Panel with LCD Display (2 Lines x 20 characters),
8 Function Keys,
12 LED Status Indicators
Available Options
Construction - Open chassis type or enclosed (Type 1, 12, 3R, 4 & 4X).
Bypass - Air and Vacuum bypass contactors are available.
Electronic DC Injection Braking