PreparationforMounting
Lifttheunitintopositionwitha
craneorforklift.Craneliftfromthe
endsofthesupportrailsusinga
spreaderbar.Whenusingafork,
liftfromunderbothsupportrails.
Ceiling Mounting
Hangceilingsupportedunitswith
four3/4-inchsteelrods,one
connectedtoeachcornerofthe
supportrail.Uselargeheavy
gaugewasherstoinsuretheunit
remainsattachedtotherods.
FloorMounting
Beforeunitstartup,always
removetheshippinghold-down
screwsfromthebottomoftheunit
tofreetheisolators.Thereisone
screwateachendofthehat
section.Usetheplugbuttons
(providedinthebagattachedto
theunit)tocovertheholes.
18 QFNA-IOM-1
Installation—SuperQIIFigure11a—InletVaneInstallation