Kunkle Safety and Relief Products

Models 910, 911, 912, 913, 916, 917, 918, 919, 920, 921 and 927

Models 920, 921, 927

ASME Section I Steam (English, lb/h) - Flow Coefficient = 0.8781

Set Pressure ——––——––————Orifice Area, in2 ———––––––————

(psig) D E F G H J

(0.1213) (0.2157) (0.3369) (0.553) (0.864) (1.415)

15

174

309

482

792

1237

2026

25

228

406

635

1042

1628

2665

35

283

504

787

1292

2018

3305

 

 

 

 

 

 

 

45

338

601

939

1541

2408

3944

55

393

699

1091

1791

2798

4583

 

 

 

 

 

 

 

65

448

796

1243

2041

3189

5222

75

504

896

1399

2297

3589

5877

 

 

 

 

 

 

 

85

560

996

1556

2554

3991

6536

95

617

1097

1713

2812

4393

7194

 

 

 

 

 

 

 

100

645

1147

1791

2940

4594

7523

125

786

1398

2183

3583

5599

9169

 

 

 

 

 

 

 

150

927

1649

2575

4227

6604

10815

175

1068

1900

2967

4870

7609

12461

 

 

 

 

 

 

 

200

1209

2150

3359

5513

8614

14107

225

1350

2401

3751

6156

9619

15753

 

 

 

 

 

 

 

250

1492

2652

4143

6800

10624

17399

275

1633

2903

4534

7443

11629

19045

 

 

 

 

 

 

 

300

1774

3154

4926

8086

12634

20691

325

1915

3405

5318

8730

13639

22337

 

 

 

 

 

 

 

350

2056

3656

5710

9373

14644

23983

375

2197

3907

6102

10016

15649

25629

 

 

 

 

 

 

 

400

2338

4158

6494

10659

16654

27275

425

2479

4409

6886

11303

17659

28921

 

 

 

 

 

 

 

450

2620

4660

7278

11946

18664

30567

475

2761

4910

7670

12589

19669

32212

 

 

 

 

 

 

 

500

2902

5161

8061

13232

20674

33858

525

3044

5412

8453

13876

 

 

 

 

 

 

 

550

3185

5663

8845

14519

575

3326

5914

9237

15162

 

 

 

 

 

 

 

600

3467

6165

9629

15805

625

3608

6416

 

 

 

 

 

 

 

650

3749

6667

675

3890

6918

 

 

 

 

 

 

 

700

4031

7169

725

4172

7419

 

 

 

 

 

 

 

750

4313

7670

775

4455

7921

 

 

 

 

 

 

 

800

4596

8172

Note

1.Pressure and Temperature Limitations Steam Section I - ‘V’ Special Use

15 to 800 psig -20° to 800°F

Tyco reserves the right to change product design and specifications

KUKMC-0392

without notice. Copyright © 2002 by Tyco International Ltd.