FLOOR PROTECTOR
Your wood stove should be placed on a 1 inch,
Convert specification to
Example:
If the floor protector is 4” brick with a
factor of 0.29 the total
1/8” mineral board K=0.29, R=1/0.29 x 0.125=0.431 Total R = Rbrick + Rmineral = 0.8 + 0.431 = 1.231 Total R is greater than 1.2, the system is acceptable.
The floor protector should exceed the stove as follows:
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Model | Front | Sides | Rear |
|
|
|
|
|
|
|
|
|
| 2000 | 25” | 8” | 6” |
|
|
|
|
|
|
|
|
|
| 2500 | 26” | 8” | 6” |
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|