3.3PIPE CONNECTOR AND DAMPER

Before proceeding to connection, remove all accessories such as scraper, shovel and poker from the evacuation pipe of the furnace.

A 7” diameter chimney listed for use with wood burning heating appliances is highly recommended for the Hotblast 1950. In this case, a reducer from 7” to 6” is required. If draft exceed –0.06 in. W.C a barometric damper should be installed on the smoke pipe. Never install a manual damper.

REDUCER

DIAMETER 7 "

For a proper installation, follow the advices below:

1. All the joints of the evacuation pipe must be secured, using three screws.

Make sure that each screw goes through the inner walls of both connectors (male and female). See pictures below showing a male-female coupling.

PROPER INSTALLATION

 

IMPROPER INSTALLATION

 

 

 

CAUSE RESTRICTION

2. A minimum rise of 1/4 inch per horizontal foot must be respected.

6