A.12 ■Appendix Watlow Series 93
Appendix
Specifications (1639)
Control Mode
• Microprocessor-based, user-selectable control modes
• Single input, dual output
• 2.5Hz Input Sampling Rate
• 1Hz Display Update Rate
• Ramp to set point: 0 to 9999 degrees or units per hour
• Heat and cool autotune
Operator Interface
• Sealed membrane front panel
• Dual, four-digit red or green displays
•‰Advance, ¿Up-arrow, ¯Down-arrow, and ˆInfinity keys
• User-selectable screen display
Accuracy
• Calibration accuracy and sensor conformity: ±0.1% of span, ±1°C
@ 25°C ±3°C (77°F ± 5°F) ambient and rated line voltage
• Accuracy span: 540°C (1000°F) minimum
• Temperature stability: ±0.2°C/°C (±0.2°F/°F) rise in ambient maxi-
mum
Sensors/Inputs
• Thermocouple, grounded or ungrounded sensors
• RTD 2- or 3-wire, platinum, 100Ω@ 0°C calibration to DIN curve
(0.00385Ω/Ω/°C) or JIS curve (0.003916Ω/Ω/°C); user-selectable
• Process, 4-20mA @ 5Ω, or 0-5VÎ(dc) @ 10kΩinput impedance
• Sensor break protection de-energizes control output to protect
system or selectable bumpless transfer to manual operation
• °C or °F or process units display, user-selectable
Input Range
Specified temperature ranges represent the controller’s operation-
al span.
• Thermocouple
Type J 0 to 750°C
(32 to 1382°F)
Type K -200 to 1250°C
(-328 to 2282°F)
Type N 0 to 1250°C
(32 to 2282°F)
Type S 0 to 1450°C
(32 to 2642°F)
Type T -200 to 350°C
(-328 to 662°F)
• RTD Resolution (DIN or JIS)
1° -200 to 700°C
(-328 to 1292°F)
0.1° -128.8 to 537.7°C
(-199.9 to 999.9°F)
• Process
4-20mA @ 5Ω, or -999 to 9999 units
0-5V (dc) @ 10kΩ, or -999 to 9999 units
Output 1(Heating or Cooling)
• Electromechanical relay1, Form C, 5A @ 120/240V~ (ac) maxi-
mum, without contact suppression, rated resistive load, 5A @
30VÎ(dc)3. Minimum contact current, 100mA @ 5VÎ(dc).
• Switched dc signal provides a non-isolated minimum turn on volt-
age of 3VÎ(dc) into a minimum 500Ωload; maximum on voltage
not greater than 12VÎ(dc) into an infinite load.
• 4-20mA reverse or direct acting, non-isolated 0 to 800Ωload.
• Solid-state relay3, Form A, 0.5A @ 24V~ (ac) min., 264V~ (ac)
max., opto-isolated burst fire switched, without contact suppres-
sion. Off-state output impedance is 31MΩ.
Output 2(Heat, Cool or Alarm)
• Electromechanical relay1, Form C, 5A @ 120/240V~ (ac) maxi-
mum, without contact suppression, rated resistive load, 5A @
30VÎ(dc)3. Minimum contact current, 100mA @ 5VÎ(dc).
• Switched dc signal provides a non-isolated minimum turn on volt-
age of 3VÎ(dc) into a minimum 500Ωload; maximum on voltage
not greater than 12VÎ(dc) into an infinite load.
• Solid-state relay3, Form A, 0.5A @ 24V~ (ac) min., 264V~ (ac)
max., opto-isolated burst fire switched, without contact suppres-
sion. Off-state output impedance is 31MΩ.
• Alarm output can be latching or non-latching, and process or devi-
ation with separate high and low values. Alarm silencing (inhibit)
on power up (for deviation alarms only).
Output Configurations
• Output 1
User-selectable as: on-off: P, PI, PD, PID, heat or cool action
• Adjustable switching differential: 1 to 55°C (1 to 99°F)
• Proportional band: 0 (off) or 0 to 555°C (1 to 999°F) or 0.0 to
999.9 units
Integral: 0 (off) or 0.1 to 99.9 minutes per repeat
Reset: 0 (off) or 0.01 to 9.99 repeats per minute
Rate/derivative: 0 (off) or 0.01 to 9.99 minutes
Cycle time: 0.1 to 999.9 seconds
• Output 2
User selectable as: Control with action opposite that of Output 1
(heating or cooling)
• Process or deviation alarm with flashing alarm message
• Process or deviation alarm without alarm message
• Alarm with separate high and low set points
• Hysteresis: 1 to 9999°or units switching differential
Line Voltage/Power
• 100-240V~ (ac), -15%, +10%4; (85-264V~ [ac]) 50/60Hz, ±5%
• 12-24Vı(ac/dc), +10%, -15%; (10-26Vı[ac/dc]) 50/60Hz, ±5%
• Fused internally(factory replaceable only) Slo-Blo®type (time-lag):
1A, 250V for high voltage versions
2A, 250V for low voltage versions
• Maximum power consumption: 12VA (100 to 240V~), 7VA (12 to
24Vı)
• Data retention upon power failure via non-volatile memory
Operating Environment4
• 0 to 65°C (32 to 149°F).
• 0 to 90% RH, non-condensing
Storage Temperature
• -40°to 85°C (-40° to 185°F)
Terminals
• #6 compression universal head screw terminals, accepts 20-14
gauge wire
Controller Weight
• 0.2 kg (0.4 lb)
Shipping Weight
• 0.34 kg(0.75 lb)
Dimensions
• Compact 1⁄16 DIN size and IP652(NEMA 4X), front panel make
the Series 93 easy to apply and maintain in a wide variety of
applications. The unique mounting bezel, gasket and collar make
installation a snap.
Overall Height: 55 mm (2.1 inches)
Width: 55 mm (2.1 inches)
Depth: 120 mm (4.7 inches)
Bezel Height: 55 mm (2.1 inches)
Width: 55 mm (2.1 inches)
Depth: 15 mm (0.6 inches)
Chassis Height: 45 mm (1.8 inches)
Width: 45 mm (1.8 inches)
Depth: 105 mm (4.1 inches)
Agency Approvals
• UL508®, c-UL, CE, IP65 (NEMA 4X), File #E102269
• CE:
89/336/EEC (EN 50082-2, EN 50081-2)
73/23/EEC (EN61010-1)
1Electromechanical relays warranted for 100,000 closures only.
Solid-state switching devices recommended for applications
requiring fast cycle times or extended service life.
2To effect IP65 (NEMA 4X) rating requires a minimum mounting
panel thickness of 1.5 mm (0.06 inch) and surface finish not
rougher than 0.000812 mm (0.000032 inch).
3Switching inductive loads (relay coils, etc.) requires using an RC
suppressor.
4Operating environment is 0 to 60°C for live voltage exceeding 240V.
Specifications