Specifications

Power Bases

Single phase, (2 SCRs)

3 phase, 2 leg control, (4 SCRs) Resistive load only, zero cross firing only

3 phase, 3 leg control, (6 SCRs)

3 phase, 3 leg control, (6 SCRs) for 4-wire wye loads

Multizone, two and three single-phase zones

Output Control Options

Zero cross contactor, VÎ(dc) input

Zero cross control, fixed time base

Time base one or four seconds with digital programmer

Zero cross control, variable time base

Phase angle control and phase angle control with current limit (not for 3-phase, 2-leg models)

Soft start factory default four seconds upon power-up, and adjustable from 0.0 to 120 seconds

Soft start upon input signal change, output rate of change adjustable to limit max rate of change from 0.1 to 100 percent per 0.1 second. Factory default 10 percent

Current transformer included when required

Line voltage compensated (variable time base and phase angle controllers only)

Standby or non-operational mode

Output Voltage and Current Rating

24 to 120VÅ(ac) (+10 percent, -15 percent)

200 to 480VÅ(ac) (+10 percent, -15 percent)

200 to 600VÅ(ac) (+10 percent, -15 percent)

65 through 250 amps per pole, model dependent; see Output Amperage Chart and Rating Curves

Minimum load 1 amp rms ac

Maximum leakage current 5mA

Alarms

Single alarm relay

Latching or non-latching

Separate high and low values

Alarm silencing (inhibit) on power up for alarm

Alarm indication LEDs, shorted SCR, open heater, fuse

Electromechanical relay, form C contact, software configurable

Minimum load current 10mA @ 5VÎ(dc)

Rated resistive loads: 3 amps @ 250VÅ(ac) or 30VÎ(dc)

max., inductive load rating 1.5 amps with a power factor ￿ 0.4 without contact suppression

Heater Bakeout

For single-phase (phase to neutral) and 3-phase 6 SCR models only (not for 3-phase, 2-leg models)

Soft start with over current trip, runs until programmed bakeout time expires, then goes burst or phase angle firing. Factory default of 24 hours

Adjustable 0 - 9999 minutes with over current trip

Internal current transformer included

Command Signal InputAnalog

Field selectable linear voltage and current of low and high points within 0-20mA and 0-10VÎ(dc)

Manual control input through front panel

Factory default 4-20mA input

Voltage input impedance 11kW nominal

Current input impedance 100W nominal

Digital

On-board digital programmer/display and optional serial communications

Retransmit

Field selectable and scalable within 0-20mA,

800W maximum or 0-10VÎ(dc), load, 1KW minimum load. The default is 4-20mA

Resolution:

mA ranges = ±5µA

VÎ(dc) = ranges 2.5mV nominal

Calibration accuracy: mA ranges = ±20µA

VÎ(dc) ranges = 10mV nominal

Temperature stability: 100ppm°C

Digital Programmer/Display and Communications Capabilities

Programming functions

Adjust input and output control type, alarms and soft start, heater bakeout and current limit prompts

Monitoring functions

Display input and output values along with actual output current

Data retention of digital programmer/display upon power failure via nonvolatile memory

Serial Communications

RS-232 for single drop control

EIA-485 for single or multidrop control

32 units maximum can be connected.With additional

485 repeater hardware, up to 247 units may be connected

Isolated

ModbusRTU protocol

1200, 2400, 4800, 9600, 19200 baud rates

Controller Power Supply

Universal line voltage input range 100 to 240VÅ(ac)

(+10 percent, -15 percent) at 55VA max

50/60Hz ± 5 percent line frequency independent

Controller line voltage for electronic power supply can be run on separate line voltage

Natural Convection and Fan Cooled Models

Cabinet venting may be required

See Amperage chart on the back page for all models.

Power Dissipation (Watts)

Approximately 1.25 watts/amp per controlled leg

Isolation

Command signal to load and line/load to ground 2200VÅ(ac) minimum

On-board semiconductor fuses provide SCR protection

Mounting

Mounts on a removable subplate

Heat sink fins must be mounted in vertical orientation

High Current Terminals

Touch safe

10 mm (38 in.) Allen head compression terminals will accept #6 AWG to 350 MCM wire. Allen wrench adapter (included) for 10 mm (38 in.) socket, 6 point only

Torque to 180 in.-lbs (20.3 Nm)

Wire strip to 30 mm (118 in.)

Controller Terminals

Touch safe

2.5 mm (18 in.) blade screwdriver, accepts 12-22 AWG or 2 No. 22-18 AWG wires

Torque to 8 in.-lbs (0.9 Nm)

Wire strip to 6 mm (0.24 in.)

Operating Environment

50°C (122°F) base rating

0 to 60°C (32 to 140°F) fan cooled

0 to 65°C (32 to 149°F) natural convection cooled

0 to 90 percent RH, non-condensing

Meets EN50178, Pollution degree three

Storage Temperature

-40 to 85°C (-40 to 185°F)

Shipping Weight

10.3 kg (23 lbs)

Agency Approvals

UL® 508 listed, File #E73741, Vol. three, Sec.two

C-UL®listed to C22.2 NO. 14

VDE EN 50178 License 115054

CE 89/336/EEC (EN61326), Class A with filter, CE 73/23/EEC (EN50178)

Modbus™ is a trademark of Schneider Automation, Inc.