Weil-McLain 801CRD, 702CRD-W, 1050FFD-W Burner specifications and settings, Notes for and Table

Models: 1150FFD 801CRD 1050FFD-W 702CRD-W

1 4
Download 4 pages 22.43 Kb
Page 2
Image 2
Burner specifications and settings

Weil-McLain 88 Water and Steam Boilers — Series 2 — For Light Oil-Fired Burners

Burner specifications and settings

Table 1

Burner data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Burner Input

Low Fire

Positive

Standard

 

 

Approximate

Boiler

 

Standard

Starting

Air Settings

 

(Forced Draft)

Firing Rate

Pressure In

Burner

Model

 

Combustion

Head

 

 

No. 2 Oil

No. 2 Oil

Firebox

Model

 

Number

 

Control

Setting

Low Fire

 

Gph

Gph

Inches W.C.

Designation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

488R

 

6.90

3.90

0.55

702CRD-W

60200

7/32

5/16

 

 

 

 

 

 

 

 

 

488

 

7.00

4.00

0.55

702CRD-W

60200

7/32

5/16

 

 

 

 

 

 

 

 

 

588

 

9.40

5.42

0.61

702CRD-W

60200

13/16

1/2

 

 

 

 

 

 

 

 

 

688

 

11.80

6.60

0.55

801CRD-W

60200

3/16

1/4

 

 

 

 

 

 

 

 

 

788

 

14.20

7.00

0.60

801CRD-W

60200

5/8

1/2

 

 

 

 

 

 

 

 

 

888

 

16.60

8.00

0.85

801CRD-W

60200

1

3/8

 

 

 

 

 

 

 

 

 

988R

 

17.20

8.90

0.65

1050FFD-W

60200

3/8

3/8

 

 

 

 

 

 

 

 

 

988

 

18.80

8.92

0.70

1050FFD-W

60200

1/2

1/4

 

 

 

 

 

 

 

 

 

1088R

 

20.00

9.60

0.70

1050FFD-W

60200

1/2

3/4

 

 

 

 

 

 

 

 

 

1088

 

21.50

10.10

0.70

1050FFD-W

RM7840L-1018

1/2

3/4

 

 

 

 

 

 

 

 

 

1188

 

23.50

12.00

0.75

1150FFD-W

RM7840L-1018

1/4

11/16

 

 

 

 

 

 

 

 

 

1288

 

26.00

12.54

0.75

1150FFD-W

RM7840L-1018

7/16

7/8

 

 

 

 

 

 

 

 

 

1388

 

28.50

13.44

0.80

1150FFD-W

RM7840L-1018

11/16

7/8

 

 

 

 

 

 

 

 

 

1488

 

31.00

15.10

0.75

1150FFD-W

RM7840L-1018

1

1

 

 

 

 

 

 

 

 

 

Notes for Table 1 and Table 2

1.Burner capacities listed for elevations up to 2,000 feet. For higher elevations, consult local Weil-McLain distributor/ agent or sales office.

2.Light oil ratings based on No. 2 fuel oil with heating value of 140,000 Btu per gallon.

3.Boiler-burner unit to be adjusted to achieve +0.10 inches W.C. pressure at the flue collar, resulting in positive pressure in firebox as listed.

4.Combustion Controls:

a.60200 combustion safety control uses a cadmium sulfide cell flame detector to monitor oil flame; provides inter- rupted duty, recycle type operation, latch-up feature, 30-second oil valve delay on, 30-second post purge, alarm contacts and safety monitor circuit.

b.RM7840L-1018 combustion safety control (for over 20 GPH applications) uses an ultraviolet flame detector to monitor oil flame and provides purge timings.

5.All motors furnished with integral overload protection with manual reset.

6.Mechanical pressure atomizing oil control system with on/ off operation, low fire start, high fire run and two-position air control is standard. Low-High-Low fire operation can be obtained by addition of SPST temperature or pressure controller.

7.120/60/1 control circuit is used for all burners.