12a Install Burner
To install burner:
1.Unpack burner.
2.Place gasket around air tube and against burner mounting flange. If sealing rope is used, apply 1/8" continuous bead of rope adhesive around burner mounting flange and apply sealing rope to make
3.Mount burner into opening in burner mounting plate.
Maintain
4.Level burner using burner support brackets where required.
5.Secure with furnished bolts.
6.Retain burner information packet. Keep with boiler.
13a Wiring and Fuel Piping
Electric shock hazard. Can cause severe personal injury or death if power source is not disconnected before installing or servicing boiler and burner.
To wire burner and boiler controls:
1.Install all wiring in compliance with:
•National Electrical Code ANSI/NFPA 70.
•Any additional national, state, or local codes.
2.Follow burner manual and wiring diagram found in burner information packet.
3.Use 14 ga. wire for operating and safety circuit wiring.
4.Where burner motor voltage differs from control voltage, supply proper voltage to each. Size fused disconnect(s) and conductors per National Electrical Code ANSI/ NFPA 70.
To install gas and/or oil piping:
1.Install all piping in compliance with:
•Local, state or national codes and regulations.
•Separate burner manual provided with burner.
2.Use pipe joint compound (pipe dope) resistant to corrosive action of fuel oil or liquified petroleum gases. Apply sparingly to male threads of pipe joints. Do not use any kind of pipe tape.
3.Oil piping - use
Do not use compression or soldered fittings. No safe repair can be made. Severe personal injury, death or substantial property damage will result.
24 | Part No. |