Burner specifications and settings (continued)

Burner Specification & Data sheet — Beckett Oil Burners

Burner specifications and settings (continued)

Table 2

Burner data, continued

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boiler

 

 

 

 

Oil Nozzle(s)

 

 

 

 

Operating Oil

Fuel Unit

 

Model

 

 

 

 

 

 

 

 

 

 

Pressures

Burner-Motor Driven

 

Preferred nozzles

 

 

Alternate nozzles

 

Number

 

 

 

 

PSIG

3450 RPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Qty.

Size

Brand

Type

Spray

Qty.

Size

Brand

Type

Spray

Low

High

Type

Nozzle

Gearset

 

 

GPH

 

 

Angle

 

GPH

 

 

Angle

Fire

Fire

(Suntec)

Capacity

Capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GPH

GPH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

488R

1

4.00

Delavan

B

70°

 

 

None

 

 

150

290

B2TA-8851

16

33

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

488

1

4.00

Delavan

B

70°

 

 

None

 

 

150

300

B2TA-8851

16

33

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

588

1

5.50

Hago

P

60°

1

5.50

Delavan

B

60°

150

300

B2TA-8851

16

33

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

688

1

7.00

Delavan

B

60°

 

 

None

 

 

150

300

B2GA-8852

23

39

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

788

1

8.50

Delavan

B

60°

1

8.50

Hago

P

60°

150

300

J4PA-C1050G

30

46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

888

2

5.00

Delavan

B

60°

2

5.00

Monarch

PLP

45°

300

300

J4PA-C1050G

30

46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

988R

2

5.50

Hago

P

60°

2

5.50

Delavan

B

60°

290

290

J4PA-C1050G

30

46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

988

2

5.50

Hago

P

60°

2

5.50

Delavan

B

60°

300

300

J4PA-C1050G

30

46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1088R

2

6.00

Delavan

B

70°

2

6.00

Delavan

B

60°

300

300

J4PA-C1050G

30

46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1088

2

6.50

Delavan

B

70°

2

6.50

Delavan

B

60°

300

300

J4PA-C1050G

30

46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1188

2

7.00

Delavan

B

45°

2

7.00

Delavan

B

60°

300

300

J4PA-C1050G

30

46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1288

2

7.50

Delavan

B

45°

2

7.50

Monarch

PLP

45°

300

300

J4PA-C1050G

30

46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1388

2

8.50

Delavan

B

60°

2

8.50

Hago

P

45°

300

300

J4PA-C1050G

30

46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes for Table 1 and Table 2

1.Burner capacities listed for elevations up to 2,000 feet. For higher elevations, consult local Weil-McLain distributor/ agent or sales office.

2.Light oil ratings based on No. 2 fuel oil with heating value of 140,000 Btu per gallon.

3.Boiler-burner unit to be adjusted to achieve +0.10 inches W.C. pressure at the flue collar, resulting in positive pressure in firebox as listed.

4.Control Systems:

LHO: On-off operation, low fire start, high fire run. Two-position air, two-position oil.

LHL: Low-high-low-off firing conditions. Two- position air, two-position oil.

5.120/60/1 control circuit is used for all burners.

6.Combustion Controls:

a)Beckett 7505P1515/CC combustion control uses

cadmium cell for flame detector to monitor oil burner flame, also furnishes intermittent ignition.

b)RM7840M flame safeguard control monitors the oil burner flame, provides pre-purge and post-purge programming. Timed low fire start is provided by means of timing built into control. Control is used with UL on-off (low fire start) systems. Photocell electronic flame detector is standard with ultraviolet and infrared detector available.

7.Burners will be completely assembled and wired.

8.Burners listed by Underwriters Laboratories, Inc., Underwrit- ers Laboratory Canada, State of Connecticut, Fire Marshal state of Massachusetts, city of New York MEA, and others.

9.Settings shown are for initial set-up. Final settings should be determined after combustion readings.

Part No. 550-142-026/0508

3

Page 3
Image 3
Weil-McLain CF3500A-W, CF1400-W, CF2500-W, CF2300A-W Burner specifications and settings continued, Notes for and Table