CGt SERIES BOILER
SUGGESTED SPECIFICATIONS
I.General Requirements
A. Furnish and install ( ) low pressure packaged cast iron sectional boiler(s) that operate under induced draft.
B.Install
C.
1.Packaged boiler (standard).
2.Natural or propane gas fired.
3.Water.
4.Minimum 82% efficiency.
5.Induced draft.
6.
D.Boiler(s) shall have I=B=R Hydronics Institute gross output(s) at 100% firing rate – 108 MBH per boiler.
E.Boiler(s) shall be manufactured by ISO 9001 registered company to conform to Section IV of
the ASME Boiler and Pressure Vessel Code.
1.Individual sections (and section assembly) to be hydrostatically pressure tested at factory in accordance with ASME requirements.
2.Maximum allowable working pressure 50 PSIG water and cast as part of section with ASME symbol.
F.Regulatory Requirements
1.Boiler(s) and controls to comply with applicable regulations.
G.Submittals
1.Submit shop drawings and product data.
2.Submittal packet to include boiler (and burner) manufacturer descriptive literature, installation instructions, operating instructions, and maintenance instructions.
II.Product
1