GOLD CGa Gas-Fired Water Boiler
44 Part Number 550-110-593/1099
Service and maintenance — schedule10a
Follow the Service and maintenance procedures given throughout this manual and in component literature
shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler or
system. Failure to follow the directions in this manual and component literature could result in severe personal
injury, death or substantial property damage.
Table 6 Service and maintenance schedules (service technician and user)

Service technician

(see following pages for instructions)

Owner maintenance

(see CGa User’s Information Manual for instructions)

ANNNUAL START-UP

Inspect:
• Reported problems
• Boiler area
• Air openings
• Flue gas vent system
• Pilot and main burner flames
• Water piping
• Boiler heating surfaces
• Burners and base
Service:
• Oiled-bearing circulators
Start-up:
• Perform start-up per manual
Check/test:
• Gas piping
• Cold fill and operating pressures
• Air vents and air elimination
• Limit controls and cutoffs
• Expansion tank
• Boiler relief valve
Review:
• Review with owner
Daily
• Check boiler area
• Check air openings
• Check boiler pressure/
temperature gauge
Monthly
• Check boiler interior piping
• Check venting system
• Check air vents
• Check boiler relief valve
• Check automatic air vents (if
used)
Periodically • Test low water cutoff (if used)
Every 6 months • Operate relief valve
End of season • Shut down procedure