GOLD CGa Gas-Fired Water Boiler
18 Part Number 550-110-593/1099
Water piping — multiple zonesFailure to prevent low return water temperature to the boiler could cause corrosion of the
boiler sections or burners, resulting in severe personal injury, death or substantial property
damage.
Radiant heating systems
Preferably, use primary/secondary piping, as shown in Figures 13 or14on page 21. Alternatively,
use the method of either Figure 15 or Figure 16 on page 23. Do not use the piping of Figure
17 (system-bypass), because this method does not control radiant system supply temperature.
If radiant system tubing has no oxygen barrier, a heat exchanger must be used.