Weil-McLain 88 Water and Steam Boilers — Series 2 — For Gas, Light Oil, & Gas/Light Oil-Fired Burners

Burner specifications and settings

Table 1

 

Burner data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Burner Input

Positive

 

Standard

 

 

Standard

 

 

 

Standard

 

Burner Motor

Standard

Boiler

 

Burner Model Designation

Combustion Control

 

Control System

 

3450 Rpm

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

 

 

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas/

No. 2 Oil

Gas

In Firebox

Gas

Light

 

Gas

Light

Gas/Light

Gas

 

Light

Gas/Light

Gas

 

Light

 

Voltage

Number

 

 

 

 

Gas/Light Oil

 

 

 

Light

 

 

Gph

 

Mbh

In. W.C.

 

Oil

 

Oil

Oil

 

 

Oil

Oil

 

 

Oil

 

 

 

 

 

 

 

 

 

 

 

 

 

Oil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

488R

 

6.9

 

996

0.80

WCR1-G-12

WCR1-OS

WCR1-GO-12

RM7897A

R7184P

RM7897C

OO

 

FALFS

OO/FALFS

Z\x

 

Z\x

 

Z\x

120/60/1

488

 

7.0

 

1,010

0.80

WCR1-G-12

WCR1-OS

WCR1-GO-12

RM7897A

R7184P

RM7897C

OO

 

FALFS

OO/FALFS

Z\x

 

Z\x

 

Z\x

120/60/1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

588

 

9.4

 

1,356

0.58

WCR1-G-12

WCR1-OS

WCR1-GO-12

RM7897A

R7184P

RM7897C

OO

 

FALFS

OO/FALFS

Z\x

 

Z\x

 

Z\x

120/60/1

688

 

11.8

 

1,701

0.46

WCR2-G-15

WCR2-OAS

WCR2-GO-15

RM7897A

R7184P

RM7897C

LHO

 

LHO

LHO/LHO

Z\x

 

C\v

 

C\v

120/60/1

788

 

14.2

 

2,046

0.47

WCR2-G-15

WCR2-OAS

WCR2-GO-15

RM7897A

R7184P

RM7897C

LHO

 

LHO

LHO/LHO

Z\x

 

C\v

 

C\v

120/60/1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

888

 

16.6

 

2,382

0.49

WCR2-G-20A

WCR2-OBS

WCR2-GO-20A

RM7897A

R7184P

RM7897C

LHO

 

LHO

LHO/LHO

C\v

 

1

 

1

240/60/1

988R

 

17.2

 

2,482

0.50

WCR2-G-20B

WCR2-OBS

WCR2-GO-20B

RM7897A

R7184P

RM7897C

LHO

 

LHO

LHO/LHO

1

 

1

 

1

240/60/1

988

 

18.8

 

2,737

0.50

WCR2-G-20B

WCR2-OBS

WCR2-GO-20B

RM7897C

R7184P

RM7897C

LHO

 

LHO

LHO/LHO

1

 

1Z\x

 

1Z\x

240/60/1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1088R

 

20.0

 

2,887

0.52

WCR2-G-20B

WCR2-OBS

WCR2-GO-20B

RM7897C

RM7897A

RM7897C

LHO

 

LHO

LHO/LHO

1

 

1Z\x

 

1Z\x

240/60/1

1088

 

21.5

 

3,082

0.73

WCR3-G-20

WCR3-O

WCR3-GO-20

RM7897C

RM7897A

RM7897C

LHO

 

LHO

LHO/LHO

1Z\x

 

2

 

2

240/60/1

1188

 

23.5

 

3,428

0.53

WCR3-G-20

WCR3-O

WCR3-GO-20

RM7897C

RM7897A

RM7897C

LHO

 

LHO

LHO/LHO

1Z\x

 

2

 

2

3-Phase*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1288

 

26.0

 

3,773

0.48

WCR3-G-20

WCR3-O

WCR3-GO-20

RM7897C

RM7897A

RM7897C

LHO

 

LHO

LHO/LHO

1Z\x

 

2

 

2

3-Phase*

1388

 

28.5

 

4,119

0.56

WCR3-G-25

WCR3-O

WCR3-GO-25

RM7897C

RM7840L

RM7840L

LHO

 

LHO

LHO/LHO

1Z\x

 

2

 

2

3-Phase*

1488

 

31.0

 

4,464

0.58

WCR3-G-25B

WCR3-OB

WCR3-GO-25B

RM7840L

RM7840L

RM7840L

LHO

 

LHO

LHO/LHO

3

 

3

 

3

3-Phase*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1588

 

33.0

 

4,809

0.59

WCR3-G-25B

WCR3-OB

WCR3-GO-25B

RM7840L

RM7840L

RM7840L

LHO

 

LHO

LHO/LHO

3

 

3

 

3

3-Phase*

1688R

 

34.5

 

4,979

0.80

WCR3-G-25B

WCR3-OB

WCR3-GO-25B

RM7840L

RM7840L

RM7840L

LHO

 

LHO

LHO/LHO

3

 

3

 

3

3-Phase*

1688

 

35.5

 

5,155

0.80

WCR3-G-25B

WCR3-OB

WCR3-GO-25B

RM7840L

RM7840L

RM7840L

LHO

 

LHO

LHO/LHO

3

 

3

 

3

3-Phase*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1788

 

38.0

 

5,494

0.62

WCR4-G-25

WCR4-OA

WCR4-GO-25

RM7840L

RM7840L

RM7840L

LHO

 

LHO

LHO/LHO

3

 

5

 

5

3-Phase*

1888

 

40.5

 

5,845

0.69

WCR4-G-25

WCR4-OA

WCR4-GO-25

RM7840L

RM7840L

RM7840L

LHO

 

LHO

LHO/LHO

3

 

5

 

5

3-Phase*

 

 

 

 

 

 

 

* 208/60/3, 240/60/3, 480/60/3 burner motor voltage must be specified.

 

 

 

 

 

 

 

Notes for Table 1 and Table 2

1.Burner capacities listed for elevations up to 2,000 feet. For higher eleva- tions, consult local Weil-McLain distributor/agent or sales office.

2.Light oil ratings based on No. 2 fuel oil with heating value of 140,000 Btu per gallon.

3.Gas ratings based on natural gas with heating value of 1,000 Btu per cubic foot and specific gravity of 0.60. Gas burners for other gases are available. Consult local Weil-McLain distributor/agent or sales office.

4.Boiler-burner unit to be adjusted to achieve +0.10 inches W.C. pressure at the flue collar, resulting in positive pressure in firebox as listed.

5.Minimum gas pressures listed are subject to variations due to job condi- tions. Gas burners for other gas pressures are available. Consult local Weil-McLain distributor/agent or sales office.

6.Tee pressures shown are for initial start-up. Final pressure should be determined after checking actual gas flow and combustion readings.

7.120/60/1 control circuit is used for all burners.

8.Control circuit transformer is available as an option.

9.Motor relay or contactor will be furnished for all units, except 488R and 488.

10.Airflow safety switch is standard for all gas and combination gas/light oil units.

11.Burners will be completely assembled and wired (except gas train) and factory test-fired.

12.Burners listed by Underwriters Laboratories, Inc., state of Connecti- cut, Fire Marshal state of Massachusetts, city of New York MEA, and others.

13.Special controls can be provided to meet other code requirements not listed. Consult your local Weil-McLain distributor/agent or sales office.

14.Electric gas pilot will be furnished as standard equipment on all gas and combination gas/light oil units.

15.Direct spark ignition is standard for light oil units. Direct spark ignition is available as an option for combination gas/light oil units. Consult your local Weil-McLain distributor/agent or sales office.

16.Gas Control Systems:

OOOn-off operation, low fire start, high fire run. Single-position air, adjustable opening gas valve.

LHO

On-off operation, low fire start, high fire run. 488-1388:

 

two-position air controlled by damper arm on motorized gas

 

valve, fixed damper pre-purge. 1488-1888: two-position air

 

controlled by separate motor, open damper pre-purge.

LHL

Low-high-low-off firing conditions. 488-1388: two-position

 

air controlled by damper arm on motorized gas valve, fixed

 

damper pre-purge. 1488-1888: two-position air controlled by

 

separate motor, open damper pre-purge.

MOD

On-off operation, with proven low fire start and full modulating

 

firing conditions with combustion air control. Proportional

 

motor drives fuel metering valve and combustion air damper

 

according to the firing conditions. Fixed damper pre-purge on

 

488-1388, open damper pre-purge on 1488-1888.

2

Part No. 550-142-029/0508

Page 2
Image 2
Weil-McLain WCR manual Burner data