| 36C01 |
| Combination Gas Valves |
| (24 Volt and 120 Volt Models) |
| INSTALLATION INSTRUCTIONS |
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
This
To permit replacement of a variety of valve sizes, this control is furnished with three reducer bushings (two 3⁄4” to 1⁄2” and one 1⁄2” to 3⁄8”). Also included is a conversion kit which allows this valve to be used at regulator settings of 4.2” W.C. to 11.0” W.C.
ON
PILOT OFF
MODELS AVAILABLE
Model No. | Voltage | Gas | Current |
36C01 | 24 volts | Nat. | .23 Amp |
36C01A | 120 volts | Nat. | .035 Amp |
SPECIFICATIONS
Electrical Rating: |
| CAPACITY (IN BTU PER HOUR) | ||
24 VAC, 60 Hz., 23A |
|
|
| |
| NATURAL GAS | LP GAS | ||
|
| |||
Pilot Gas Outlet: |
| (1000 Btu/Cu. Ft. | (2500 Btu/Cu. Ft. | |
Located at outlet end of the valve |
| 0.64 Sp. Gr.) | 1.53 Sp. Gr.) | |
Type of Gas: | 1⁄2” x 3⁄8” | 100,000 | 162,000 | |
1⁄2” x 1⁄2” | 230,000 | 372,600 | ||
Suitable for all domestic heating gases | ||||
1⁄2” x 3⁄4” | 230,000 | 372,600 | ||
Pressure Regulator Setting: | 3⁄4” x 3⁄4” | 280,000 | 453,600 |
Adjustable from 21⁄2 to 5” W.C. (Factory adjusted for 3.5” W.C.
Pressure Rating: 1⁄2 lb. per sq. in.
Ambient Temperature:
Mounting: Any position except
Upright, 90°from upright or vertical
UPRIGHT | INLET BOSS |
UP OR DOWN | |
| LEFT OR RIGHT |
ON
OFF
NOTE: Control shown may not be identical to replacement control.