EXPLOSION RESISTING CONTROLS

 

EXPLOSION RESISTING CONTROLS

WHITE-RODGERS

Heating Service

 

INSTALLATION INSTRUCTIONS

 

 

Operator: Save these instructions for future use!

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.

DESCRIPTION

These explosion resisting thermostats are designed for control- ling heating installations having hazardous atmospheres, such as oil refinery, coal mine, flour mill, etc. They are designed for line voltage operation, but may also be used as low voltage pilot controls. White-Rodgers explosion resisting controls are avail- able with either self-contained or remote sensitive bulbs.

The self-contained type is especially recommended for heating installations of large air space.

The remote element type is applicable to installations such as ducts, ovens or liquid baths.

THESE CONTROLS MUST BE INSTALLED BY A QUALIFIED INSTALLER.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical codes and ordinances.

This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.

This control has been accurately calibrated at the factory. Any attempt to calibrate this control will void the White-Rodgers warranty.

PRECAUTIONS

WHITE-RODGERSCAUTION

To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.

Heating ServiceWARNING

Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazard.

Switch Action: S.P.S.T. – Open on Rise

Dimensions of Enclosure: 6-1/8" high

5-1/4" wide over lugs

4-5/8" deep over adjusting knob

SPECIFICATIONS

Enclosure: Designed for Class I, Group D; Class II, Groups E, F and G locations.

Electrical Opening: 1/2" pipe thread in bottom of enclosure.

WHITE-RODGERS DIVISION

 

EMERSON ELECTRIC CO.

 

9797 REAVIS RD., ST. LOUIS, MO. 63123

 

(314) 577-1300, FAX (314) 577-1517

Printed in U.S.A.