INSTALLATION
Location
Mount the relay on a flat, solid surface inside the equipment control box. The relay may be panel- or
Wiring
Disconnect power supply before connecting wiring to prevent electrical shock or equipment damage.
All wiring must comply with local codes and ordinances.
Crimp female
Terminal designations on
No Off Delay Wiring
For No Off delay operation remove the red wire from terminal “A” and the green wire from terminal “T.” Take the red wire that was removed from terminal “A” and connect to terminal “T.” Next take the green wire that was removed from terminal “T” and connect to terminal “A.” You may hear a double click when
A B 6 T 4
3 (NO) | Refer to label on side |
1 (COM) | of relay for information |
| |
| on terminal functions. |
Fig. 1. Mounting 57T01-843 on panel
C3 | R2 | R12 | A |
| 24 VAC Rd |
|
|
| E1 | ||
|
|
|
| from Transformer | |
|
|
|
|
| |
R8 |
|
| B |
| 24 VAC Common BL |
|
|
|
| E3 | |
|
| RV1 |
| from Transformer | |
|
|
|
| ||
|
| K1 | 6 |
| WH/J to Heater Plug |
C1 R1 |
| HIGH VOLTAGE FAN |
| E4 | |
|
| Connection | |||
C5 |
|
|
|
| |
| 1 (COM) | T |
| GR from LV Field | |
|
|
| |||
|
|
|
| ||
|
|
|
| E2 | |
C6 |
|
|
| Connection | |
C7 |
| 3 (NO) | 4 |
| BL Common from |
|
|
|
| ||
| K2 |
|
| E5 | LV Field Connection |
|
|
|
|
|
Fig. 2. 57T01-843 Terminal Designations
4 1
B
T
A 6 3
Fig. 3. Mounting 57T01-843 on panel
energized which is normal.
Make sure all wires are connected to the proper terminals on the time delay board for proper system operation. Refer to Figs.
Do not exceed contact and coil ratings when wiring into system.
1 3
2
4 6 5
A
B T
TIME DELAY BOARD
TERMINAL CONNECTION
DESIGNATION
A24 Vac LINE (HOT SIDE)
B24 Vac COMMON
TFAN TERMINAL ON THERMOSTAT OR OTHER CONTROLLER
Fig. 4. 57T01-843 Circuit and terminal designations
OPERATION AND CHECKOUT
Operation
When the thermostat calls for indoor blower operation, an electronic switch in the electronic board pulls in and powers the relay coil. When the call ends, the electronic switch in the electronic board holds in the relay coil for an additional 80 seconds. This increases the efficiency of the equipment and saves energy.
NOTE: When power is initially applied during installation or after power interruption, the relay will pull in for a maximum of 0.5 seconds and then drop out.
Checkout
When power is initially applied, check to make sure the relay pulls in for not more than 0.5 seconds and drops out. Then operate the relay and controlled equipment to make sure that the relay pulls in when the T terminal is energized with 24 VAC and that controlled equipment operates as intended. Relay pulls in after a short on delay of 2 seconds (±0.7). When the T terminal is deenergized (24 VAC removed), the indoor air blower should continue to operate until the delay period (80 seconds) ends.