| INSTALLATION INSTRUCTIONS |
|
|
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
The Fan control is a normally open SPST switch which closes on a rise in temperature and has an adjustable temperature setting.
The Limit control is a normally closed SPST switch which opens on a rise in temperature to limit the maximum allowable temperature and has an adjustable tempera- ture setting.
DESCRIPTION
This control is particularly well suited for use where space limitations are a problem. The small bimetal sensing element is completely in the air stream to give quick response. This control has a
THIS CONTROL MUST BE INSTALLED BY A QUALI- FIED INSTALLER.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough handling or distorting compo- nents could cause the control to malfunction.
This control has been accurately calibrated at the factory. Any attempt to
!WARNING
Do not use on circuits exceeding specified volt- ages. Higher voltages will damage control and could cause shock or fire hazard.
If in doubt about whether your wiring is millivolt, low or line voltage, have it inspected by a quali- fied heating and air conditioning contractor or a licensed electrician.
PRECAUTIONS
!CAUTION
To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
Label all wires prior to disconnection when ser- vicing controls. Wiring errors can cause improper and dangerous operation.
Following installation or replacement, follow appliance manufacturers’ recommended instal- lation/service instructions to insure proper op- eration.
|
| SPECIFICATIONS | |
|
| ||
AC ELECTRICAL RATINGS: | Temperature Ratings: | ||
8 Amps at 120 VAC or 4 Amps at 240 VAC | Fan control - Variable 70° to 160°F (21° to 71°C). | ||
Pilot Duty: 125 VA | Fixed differential 25°F (14°C) | ||
Limit control - Variable 110° to 200°F (43° to 93°C). | |||
| |||
| Fixed differential 25°F (14°C) |
EMERSON ELECTRIC CO.
9797 REAVIS ROAD
ST. LOUIS, MISSOURI
PART NO.
Printed in U.S.A.
9721