9 RED FLASHES: Indicates reversed line voltage polarity or grounding problem. Both heating and cooling operations will be affected. Check polarity at furnace and branch. Check furnace grounding. Check that flame probe is not shorted to chassis.
10 RED FLASHES: Gas valve energized with no call for heat. Check gas valve and gas valve wiring.
11 RED FLASHES: This indicates that a primary or auxiliary limit switch has opened its
12 RED FLASHES: This code indicates an open igniter circuit, which could be caused by a disconnected or loose wire or by a cracked or bro- ken igniter.
STEADY ON RED: Control failure. Replace control board.
NOTE: If a flame is detected the control flashes the LED for 1/8 of a second and then enters a flame stabilization period.
IGNITION CONTROL
Normal flame sense current is approximately
3.7 microamps DC (µa)
Low flame signal warning starts at 1.5 microamps.
Low flame signal control lockout point is
0.1 microamps DC (µa)
DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL
The control in this furnace is equipped with memory that will store up to five error codes to allow a service technician to diagnose problems more easily. This memory will be retained even if power to the furnace is lost. This feature should only be used by a qualified service tech- nician.
The control stores up to five separate error codes. If more than five error codes have occurred since the last reset, only the five most recent will be retained. The furnace control board has a button, labeled "LAST ERROR" that is used to retrieve error codes. This function will only work if there are no active thermostat signals. So any call for heating, cooling or continuous fan must be terminated before attempting to retrieve error codes.
To retrieve the error codes, push the LAST ERROR button. The LED on the control will then flash the error codes that are in memory, starting with the most recent. There will be a
If there are no error codes in memory, the LED will flash two green flashes. To clear the memory, push the LAST ERROR button and hold it for more than five seconds. The LED will flash three green flashes when the memory has been cleared, then will resume the normal slow green flash after a
Thermostat Calling for Heat
(Seconds) | 0 2 | 17 | 22 | 52 |
Fan on Delay 30 Seconds
ON
THERMOSTAT
OFF
ON
INDUCER
OFF
ON
Thermostat Satisfied
0
OFF |
|
15 Sec. | OFF |
Post |
|
Purge |
|
IGNITOR OFF
MAIN VALVE
OFF
HUMIDIFIER
OFF
ELECTRONIC
AIR CLEANER
OFF
CIRCULATING
BLOWER OFF
OFF
ON
ON
OFF
ON
OFF
ON
OFF
OFF |
OFF
OFF
OFF
60, 90, 120, 180 SEC. OFF Selectable Fan Off Delay
FIGURE 7: Furnace Control Event Schedule
Unitary Products Group | 7 |