Wolf SRT486G 48 1219 Sealed Burner Rangetops, Planning Information, I N S T A L L A T I O N

Models: SRT484DG SRT486G

1 5
Download 5 pages 22.4 Kb
Page 5
Image 5
I N S T A L L A T I O N N O T E S

Planning Information

48" (1219) Sealed Burner Rangetops

I N S T A L L A T I O N

I N S T A L L A T I O N N O T E S

Manual background Refer to the illustrations and specifications for overall dimensions, finished rough opening dimensions and installation specifics.

IMPORTANT NOTE: Caution must be used in planning the proper installation of the Wolf sealed burner rangetop to avoid any fires or damage to adjacent cabinetry or kitchen equip- ment. Follow the minimum clearances estab- lished in the finished rough opening dimensions as shown in the Installation illustration.

The platform for the rangetop must be 3/4"

(19)thick and include a cut-out at the right rear for gas supply and electrical connections. The platform must be level to ensure that the cooking surface is level.

IMPORTANT NOTE: A minimum 10" (254) riser is required for charbroiler (C) or griddle (G) models installed against a combustible surface.

Manual background It is recommended that you use a Wolf Pro wall or island ventilation hood or hood liner with the Wolf sealed burner rangetop. Refer to the Pro Ventilation section of our website, wolfappliance.com.

Manual background The Wolf sealed burner rangetop requires a 110/120 V AC, 50/60 Hz electrical supply to operate the electronic ignition system. The power supply cord is equipped with a 3-prong, grounded plug for protection against shock hazard. The service should have its own 15 amp circuit breaker. Locate electrical and gas supply within the shaded area shown in the Installation illustration.

IMPORTANT NOTE: A ground fault circuit interrupter (GFCI) is not recommended and may cause interruption of operation.

Manual background Wolf sealed burner rangetops are designed to operate on natural gas at 5" (12.5 mb) WC (water column) pressure or LP (propane) gas at 10" (25 mb) WC pressure. The minimum line pressure for natural gas is 7" (17.5 mb) WC and 11" (27.4 mb) WC for LP gas. The maximum gas supply pressure to the regulator should never exceed 14" (34.9 mb) WC; .5 psi (3.5 kPa).

Manual background If local codes permit, a certified, 3' (.9 m) long, 1/2" or 3/4" ID flexible metal appliance connector is recommended for connecting the rangetop to the gas supply line.

IMPORTANT NOTE: A separate external gas shut-off valve must be located near the rangetop in an accessible location.

Manual background Wolf sealed burner rangetops using natural gas will operate up to an altitude of 8,000' (2438 m) without any adjustment. Natural gas and LP gas installations from 8,000' (2438 m) to 11,000' (3353 m) need the high altitude conversion kit. Contact your Wolf dealer for details. To obtain local dealer information, visit the Locator section of our website, wolfappli- ance.com.

Manual background You must follow all National Electrical Code and gas regulations. In addition, be aware of local codes and ordinances when installing your services.

Manual background Refer to the installation instructions shipped with each Wolf product for detailed specifications.

Dimensions in parentheses are in

millimeters unless otherwise specified.