Close Backwall, Rigid Conduit Electrical Connections
1.Lift the front of the griddle top only as far as necessary to gain access to the terminal box on the body’s inside rear.
2.Prop the griddle top up securely to prevent it from failing.
Do not lift the griddle top too high, as thermostat and unit terminals may be damaged beyond repair.
3.Remove the fastener near the bottom of the terminal box and slide the enclosure up to expose knockouts.
4.Connect griddle’s line leads to the supply wires as shown in the applicable wiring diagram. Do not disturb the griddle wiring.
5.Slide enclosure down and secure with fastener.
6.Lower the griddle top, making sure that it is securely in place.
Since the griddle is not fused, you must connect it to a fused circuit equipped with a suitable disconnecting means as required by local authorities.
STANDARD VOLTAGES‐208 VOLTS OR 240 VOLTS 50/60 Hz.‐SINGLE OR THREE PHASE
480 VOLTS 50/60 Hz.‐THREE PHASE ONLY
|
|
| 3 PHASE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| TOTAL | TOTAL | LOADING |
|
|
|
|
|
| NOMINAL AMPS PER LINE WIRE CONN.* |
|
| |||||||||||
MODEL | CONN. | KW | KW PER PHASE |
|
|
|
|
|
|
| 3 PHASE |
|
|
|
|
|
| 1 PHASE | |||||
NO. | KW | PER | PER CONN.* |
| 208 VOLT |
|
|
| 240 VOLT |
|
| 480 VOLT |
| 208 | 240 | ||||||||
|
| CONN | X‐Y | Y‐Z | X‐Z | X |
| Y |
| Z |
| X |
| Y |
| Z | X |
| Y |
| Z | VOLT | VOLT |
WEG24R | 8.0 | 8.0 | 4.0 | 0.0 | 4.0 | 38.5 |
| 19.3 |
| 19.3 |
| 28.9 |
| 16.7 |
| 16.7 | 14.4 |
| 8.3 |
| 8.3 | 38.5 | 33.3 |
WEG36S | 12.0 | 12.0 | 4.0 | 4.0 | 4.0 | 33.4 |
| 33.4 |
| 33.4 |
| 28.9 |
| 28.9 |
| 28.9 | 14.4 |
| 14.4 |
| 14.4 | 57.7 | 50.0 |
WEG36D | 16.2 | 16.2 | 5.4 | 5.4 | 5.4 | 45.0 |
| 45.0 |
| 45.0 |
| 39.0 |
| 39.0 |
| 39.0 | 19.5 |
| 19.5 |
| 19.5 | 77.9 | 67.5 |
WEG48D | 21.6 | 21.6 | 10.8 | 5.4 | 5.4 | 68.7 |
| 68.7 |
| 45.2 |
| 59.5 |
| 59.5 |
| 39.0 | 29.8 |
| 29.8 |
| 19.5 | 103.9 | 90.0 |
WEG60D** | 27.0 | 16.2 | 5.4 | 5.4 | 5.4 | 45.0 |
| 45.0 |
| 45.0 |
| 39.0 |
| 39.0 |
| 39.0 | 19.5 |
| 19.5 |
| 19.5 | 77.9 | 67.5 |
|
| 10.8 | 5.4 | 0.0 | 5.4 | 45.0 |
| 26.0 |
| 26.0 |
| 39.0 |
| 22.5 |
| 22.5 | 19.5 |
| 11.3 |
| 11.3 | 51.9 | 45.0 |
WEG72D* | 32.4 | 16.2 | 5.4 | 5.4 | 5.4 | 45.0 |
| 45.0 |
| 45.0 |
| 39.0 |
| 39.0 |
| 39.0 | 19.5 |
| 19.5 |
| 19.5 | 77.9 | 67.5 |
|
| 16.2 | 5.4 | 5.4 | 5.4 | 45.0 |
| 45.0 |
| 45.0 |
| 39.0 |
| 39.0 |
| 39.0 | 19.5 |
| 19.5 |
| 19.5 | 77.9 | 67.5 |
*NOTE: Two separate conduit connections must be made: each connection carries
**NOTE: Two separate conduit connections must be made: one connection carries 16.2 KW, the other connection carries 10.8 KW.
- 4 -