FUZZY LOGIC CO2 CONTROL (Continued)
CHANGING CONTROL MODES (Continued)
Changing to ON / OFF control mode
1)Press and hold the (SEL) pushbutton for three seconds. (P will be displayed)
2)Press the (SEL) button momentarily. (The current proportional band setting will be displayed = 5.0)
3)Using the (Down) pushbutton, change the display to read (0.0)
4)Momentarily press the (SEL) button to accept the change.
5)Allow the unit to
Changing to “Fuzzy Logic” control mode
1)Press and hold the (SEL) pushbutton for three seconds. (P will be displayed)
2)Press the (SEL) button momentarily. (The current proportional band setting will be displayed = 0.0)
3)Using the (Down) pushbutton, change the display to read (5.0)
4)Momentarily press the (SEL) button to accept the change.
5)Allow the unit to
*Note: There are several other “hidden” internal parameters that are normally
CALIBRATION
The
Supplying the unit with outside air can quickly verify the calibration. The reading outdoors should be around
•The
•Checking calibration in urban areas usually results in higher ambient CO2 readings due to car exhaust and human activity.
To check calibration:
1)Bring the unit outside so that it will receive fresh air. Do not locate the unit in direct sunlight.
2)Plug the power supply and power cord into 120vac.
3)Move away from the controller to allow the reading to stabilize for approximately 20 minutes.
4)Check the CO2 level.
*Important: Do not breathe while checking the calibration the unit. As you exhale, large concentrations of CO2 are expelled from your lungs. This higher level of CO2 will affect the calibration of the unit. Try to hold your breath!
5)If the level is between 250 and 550 the unit is performing fine. If it is outside that range, allow the unit to stabilize longer.
6)If the calibration is still off, the unit can be returned to the factory for