NOTE:

If you operate the generator with the voltage select switch in the 120/240V-position, the electric current will be limited for the 120V-receptacles.

When you use either receptacle 1 or 2 AND receptacle 3 at the same time, the total electric current provided will be equal to or even less than 22.9A.

For example:

If the 240V-receptacle provides 10A, the 120V-receptacles 1 and 2 can be used up to 12.9A each.

In case the load exceeds 22.9A, the overload indicator light will turn on and the generator will stop. (At this moment the segments of the powermeter may not reach 10)

If you operate the generator with the voltage select switch in the 120V-position, the receptacles 1 and 2 can supply rated current (45.8A).

1

Hour meter

The hour meter 1 shows the total number of hours

 

 

the generator has been run.

763-7CKf

 

1

763-7CKg

1

763-7CKc

Power meter

The power meter 1 shows the amount of electric current used by a barmeter.

The generator output is normal when the segments of the barmeter appear.

NOTE:

When 10 segments appear, the generator has almost reached its rated output.

AC pilot light (green)

The AC pilot light 1 comes on when the engine starts and produces power.

– 10 –