York 360101-XTG-A-0108 manual Thermostat Unit Terminal Strip, Control Wiring, Power Wiring, Blower

Models: 360101-XTG-A-0108

1 24
Download 24 pages 59.5 Kb
Page 13
Image 13
Blower
24 VOLT
TRANSFORMER

360101-XTG-A-0108

TABLE 10: SIDE AND BOTTOM SUPPLY AIR BLOWER PERFORMANCE

Model No.

Blower

 

 

 

 

 

 

External

Static Pressure (Inches Water Gauge)

 

 

 

 

 

 

 

 

DEB

Speed

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.1

 

Setting

CFM

W

CFM

W

CFM

W

CFM

W

CFM

W

CFM

W

CFM

W

CFM

W

CFM

W

CFM

W

CFM

 

W

 

 

018

High

-

-

-

-

-

-

-

-

689

374

593

361

497

347

-

-

-

-

-

-

-

 

-

Medium

-

-

-

-

-

-

690

231

659

210

487

188

-

-

-

-

-

-

-

-

-

 

-

(1.5)

 

Low

741

226

686

212

632

198

577

185

453

165

-

-

-

-

-

-

-

-

-

-

-

 

-

 

 

024

High

-

-

-

-

-

-

-

-

-

-

-

-

990

468

888

456

786

444

684

432

-

 

-

Medium

-

-

-

-

961

331

902

321

841

305

781

290

720

274

660

257

-

-

-

-

-

 

-

(2.0)

 

Low

810

261

765

250

720

238

675

227

627

212

-

-

-

-

-

-

-

-

-

-

-

 

-

 

 

030

High

-

-

-

-

-

-

-

-

1171

504

1080

486

990

468

888

456

786

444

-

-

-

 

-

Medium

1080

351

1021

341

961

331

902

321

841

305

781

290

-

-

-

-

-

-

-

-

-

 

-

(2.5)

 

Low

810

261

765

240

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

-

 

 

036

High

-

-

-

-

1440

605

1361

581

1273

555

1185

530

1097

504

1004

480

912

456

-

-

-

 

-

Medium

1465

531

1395

512

1325

492

1255

473

1167

446

1079

419

992

392

-

-

-

-

-

-

-

 

-

(3.0)

 

Low

1316

473

1260

455

1204

438

1148

420

1069

396

990

372

911

348

-

-

-

-

-

-

-

 

-

 

 

042

High

-

-

-

-

1728

725

1633

697

1527

666

1422

635

1317

605

1205

576

1094

547

-

-

-

 

-

Medium

-

-

1674

614

1590

590

1506

567

1400

535

1295

502

1190

470

1063

428

-

-

-

-

-

 

-

(3.5)

 

Low

1579

567

1512

546

1444

525

1377

504

1282

476

1188

447

1093

418

-

-

-

-

-

-

-

 

-

 

 

048

High

-

-

1985

870

1939

850

1897

830

1813

800

1728

770

1644

740

1559

707

1474

673

1389

640

-

 

-

Medium

1694

690

1662

673

1629

657

1597

640

1542

623

1486

607

1431

590

1336

563

1240

537

-

-

-

 

-

(4.0)

 

Low

1385

520

1349

510

1312

500

1276

490

1235

480

-

-

-

-

-

-

-

-

-

-

-

 

-

 

 

060

High

-

-

-

-

2450

1213

2366

1165

2282

1117

2198

1068

2114

1020

1989

993

1864

967

1739

940

-

 

-

Medium

2339

1170

2275

1118

2211

1067

2147

1015

2083

963

2019

912

1955

860

1854

824

1753

788

1652

752

-

 

-

(5.0)

 

Low

1929

940

1877

903

1824

867

1772

830

1720

793

1667

757

1615

720

1586

706

1557

691

1528

677

-

 

-

 

 

TABLE 11: ADDITIONAL STATIC RESISTANCE

 

 

 

 

 

 

Resistance, IWG

 

 

 

 

 

Description

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

600

700

800

900

1,000

 

1,100

1,200

1,300

1,400

1,500

1,600

Wet Evaporator Coil

.01

.01

.01

.02

.03

.04

 

.05

.06

.07

.08

.09

.09

Economizer

.00

.00

.00

.01

.01

.01

 

.01

.02

.03

.04

.05

.06

Filter/Frame Kit

.01

.02

.02

.02

.02

.02

 

.03

.03

.03

.03

.04

.05

Electric Heat

.02

.03

.03

.03

.04

.04

 

.05

.06

.07

.08

.09

.10

Note:1. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.

2.The pressure thru the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.

THERMOSTAT UNIT TERMINAL STRIP

** = Minimum wire size of 18 AWG

**

wire should be used for all field

 

installed 24 volt wire.

 

PROGRAMMABLE

 

THERMOSTAT ONLY

*

 

* = Only required on units with supplemental electric heat.

CONTROL WIRING

CAUTION: Label all wires prior to discon- nection when servicing con- trols. Wiring errors can cause improper and dangerous op- eration. Verify proper operation after servicing.

NOTE:

HEAT ANTICIPATOR

SHOULD BE SET AT 0.25

AMPS FOR ALL MODELS.

REFER TO ELECTRICAL

DATA TABLES TO SIZE

THE DISCONNECT

POWER WIRING

FIGURE 2 - TYPICAL FIELD WIRING DIAGRAM

Johnson Controls Unitary Products

13

Page 13
Image 13